Thermal Expansion Valves
LCL Take-Apart
Features
Stainless steel power element eliminates corrosion and
prevents valve failure
Take-Apart construction for easy eld service
The LCL Take-Apart series is a desuperheating (Liquid Injection)
valve used in conjunction with hot gas bypass to prevent excessive
suction line superheat. LCL valves can be used for interstage
cooling in compound systems.
Specifications
Maximum working pressure: 450 psig
Options
Interchangeable, replaceable cages for versatility
External superheat adjustment
Interchangeable body anges
Interchangeable power assemblies
Nomenclature example: LCLE 2 B 5 FT 3/8 x 1/2 ODF S/T
LCL E 2 B 5 FT 3/8 x 1/2 ODF S/T
Valve Series
De-Superheating
Liquid Injection
Take-Apart
Equalizer
E=External
(Omit for Internal)
Capacity
Nominal NOTE: This
is not system capacity
(Contact Application
Engineering
for sizing)
Refrigerant Code Capillary Tube Length
5 FT (std)
Inlet x Outlet Connection
Sizes
(see table below)
Connection Type
SAE = are
ODF=solder
Conguration
ANG = 90° angle
S/T = straight-thru
Ordering Information
Description Equalizer Type
PCN By Charge
ConnectionsSelect From Table Below
A B C
LCL 1
Internal
022018 022017 --
Same as
TCL &
TCLE
LCL 2 022005 021996 045527
LCL 3 055093 021987 --
LCL 6 047759 -- --
LCLE 1
1/4””SAE
External
055096 -- --
LCLE 2 022003 021997 --
LCLE 3 021991 021985 --
LCLE 4 -- 061054 055097
NOTE: Add charge sufx symbol “A”, “B”, or “C” based on the following table.
Example: LCLE4-A
LCL (LA) Charge Codes
Saturated Suction
Refrigerant
R-134A R-22 R-404A/R-507
Required Suction Gas Required Suction Gas Required Suction Gas
TEMP. 45°F 65°F 45°F 65°F 45°F 65°F
40°F -- B (GL) -- A (CL) -- --
30°F B (GL) B (GL) -- A (CL) -- A (CL)
20°F B (GL) C (UL) A (CL) B (GL) -- A (CL)
10°F B (GL) C (UL) B (GL) B (GL) A (CL) B (GL)
0°F C (UL) C (UL) B (GL) B (GL) A (CL) B (GL)
-10°F C (UL) C (UL) B (GL) C (UL) B (GL) B (GL)
-20°F C (UL) C (UL) B (GL) C (UL) B (GL) C (UL)
-30°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)
-40°F C (UL) C (UL) C (UL) C (UL) B (GL) C (UL)
( ) Denotes LA Series valve charge code.
Note: Valve sizes LCL5, LCL8, LCLE5 and
LCLE8 are OBSOLETE.
Replacement Valve Guide
If have: Replace with:
LA(E)S 1/2 LCL 1
LA(E)S 1 LCL 2
LA(E)S 2 LCL 3
LA(E)S 3 LCL 4
LA(E)S 5 LCL 6
LCL 5 LCL 6
LCLE 5 LCLE 6
LCL 8 LCL 9
LCLE 8 LCLE 9