Brochure
Emerson Climate Technologies
45
Thermal Expansion Valves
Features
•  Stainless steel power element eliminates corrosion and  
  prevents valve failure
•  Replaceable power element
•  External superheat adjustment
•  ODF connections
•  Balanced port construction compensates for changes in
  operating pressures due to varying ambients, or widely 
  varying evaporator loads
•  Bi-Directional control capacity
•  External equalizer
•  ZAA charge for R-410A systems
Specifications
•  Maximum working pressure:  630 psig
The TFE R-410A series is designed for large tonnage heat pump, air 
conditioning, and commercial refrigeration applications.
Nomenclature example: TFES 16 ZAA 5/8 x 7/8 ODF S/T
TF E S 16 Z AA 5/8 x 7/8 ODF S/T
Valve Series 
Balanced Port, 
Replaceable 
Power 
Assembly
 Equalizer 
E=External 
¼” ODF
Connection Type
S = solder
Capacity 
Nominal Rating 
in Tons 
Refrigerant Code
Z = R-410A
Charge Code
AA = wide range
Inlet x Outlet
 Connection Sizes
(See ordering 
information table 
below)
Connection 
Type 
ODF=solder
Conguration
S/T = Straight-
thru
Ordering Information
Refrigerant Tons Bleed Inlet x Outlet
Sensing Bulb  
Capillary 
Tube Length
PCN
R-410A
12
- 5/8 ODF x 7/8 ODF 5 ft. 066146
15% 5/8 ODF x 7/8 ODF 5 ft. 066147
- 7/8 ODF x 1-1/8 ODF 10 ft. 066148
16
- 5/8 ODF x 7/8 ODF 5 ft. 066149
15% 5/8 ODF x 7/8 ODF 5 ft. 066150
- 7/8 ODF x 1-1/8 ODF 10 ft. 066151
20
- 5/8 ODF x 7/8 ODF 5 ft. 066152
15% 5/8 ODF x 7/8 ODF 5 ft. 066153
- 7/8 ODF x 1-1/8 ODF 10 ft. 066154
Inlet/Outlet Fittings Dimensional Data (in)
Connections Inlet Outlet
Inlet Outlet A B MIN C D MIN.
1/2 ODF
1/2ODF 0.50 0.37 0.50 0.37
5/8 ODF 0.50 0.37 0.63 0.50
7/8ODF 0.50 0.37 0.88 0.76
5/8 ODF
5/8 ODF 0.63 0.50 0.63 0.50
7/8ODF 0.63 0.50 0.88 0.76
1-1/8 ODF 0.63 0.50 1.13 0.91
7/8 ODF
7/8ODF 0.88 0.76 0.88 0.76
1-1/8 ODF 0.88 0.76 1.13 0.91
Dimensional Data (in)
Replacement Parts
Description PCN
R-410A Power Assembly (10 ft.)* 066155*
Seal Nut 058707
*Approved for use only on TFE-Series R-410A valves (with ZAA charge)
TFE Nominal* Capacity Table in Tons
Model Typical System Application
TFE 12 10-13 Tons
TFE 16 14-17 Tons
TFE 20 18-20 Tons
*See Extended Capacity Tables for ratings at a wide range of conditions per
ARI standard 750
TFE R-410A Series