System Protector Capacity Tables
Emerson Climate Technologies
Description
R-22 R-502
-40
o
F -20
o
F 0
o
F +20
o
F +40
o
F -40
o
F -20
o
F 0
o
F +20
o
F +40
o
F
A-AS 3 84 0.40 0.60 0.90 1.40 2.00 0.30 0.50 0.80 1.30 1.80
A-AS 3 105 0.50 0.80 1.40 2.10 3.00 0.50 0.80 1.20 1.90 2.70
A-AS 3 125 0.50 0.80 1.40 2.10 3.00 0.50 0.80 1.20 1.90 2.70
A-AS 3 126 0.72 1.10 1.80 2.80 4.00 0.60 1.00 1.60 2.50 3.50
A-AS 3 145 0.50 0.80 1.40 2.10 3.00 0.60 0.80 1.20 1.90 2.70
A-AS 3 146 0.72 1.10 1.80 2.80 4.00 0.60 1.00 1.60 2.50 3.50
A-AS 4 64 0.40 0.60 0.90 1.40 2.00 0.30 0.50 0.80 1.30 1.80
A-AS 4 65 0.50 0.80 1.40 2.10 3.00 0.50 0.80 1.20 1.90 2.70
A-AS 4 105 0.50 0.80 1.40 2.10 3.00 0.50 0.80 1.20 1.90 2.70
A-AS 4 106 0.72 1.10 1.80 2.80 4.00 0.60 1.00 1.60 2.50 3.50
A-AS 5 96 0.72 1.10 1.80 2.80 4.00 0.60 1.00 1.60 2.50 3.50
A-AS 5 97 1.30 2.00 3.30 5.10 7.30 1.10 1.70 2.80 4.30 6.20
A-AS 5 126 0.72 1.10 1.80 2.80 4.00 0.60 1.00 1.60 2.50 3.50
A-AS 5 127 1.30 2.00 3.30 5.10 7.30 1.10 1.70 2.80 4.30 6.20
A-AS 5 137 1.30 2.00 3.30 5.10 7.30 1.10 1.70 2.80 4.30 6.20
A-AS 5 139 2.10 3.30 5.30 8.30 11.80 1.90 2.90 4.60 7.10 10.20
A-AS 5 179 2.10 3.30 5.30 8.30 11.80 1.90 2.90 4.60 7.10 10.20
A-AS 5 1711 3.40 5.30 8.50 13.20 18.80 3.00 4.60 7.40 11.60 16.50
A-AS 6 117 1.30 2.00 3.30 5.10 7.30 1.10 1.70 2.80 4.30 6.20
A-AS 6 137 1.30 2.00 3.30 5.10 7.30 1.10 1.70 2.80 4.30 6.20
A-AS 6 139 2.10 3.30 5.30 8.30 11.80 1.90 2.90 4.60 7.10 10.20
A-AS 6 1411 3.40 5.30 8.50 13.20 18.80 3.00 4.60 7.40 11.60 16.50
A-AS 6 1713 5.10 8.00 12.80 20.00 28.50 4.40 6.90 11.00 17.20 24.50
A-AS 6 2013 5.10 8.00 12.80 20.00 28.50 4.40 6.90 11.00 17.20 24.50
A-AS 6 2513 12.80 20.80 28.50 4.40 6.90 11.00 17.20 24.50
The maximum capacity in tons recommended is based on a pressure drop through the accumulator equivalent to 1.0
o
F.
Note: 1) The minimum system capacity in tons must be no less than 15% of the stated capacity in order to ensure a positive return of oil.
2) All of the data is based on tons of refrigeration and is not related to horsepower.
3) Minimum evaporator temperature of -40
o
F. Minimum temperature of the suction gas through the accumulator is 12
o
F.