Brochure

Emerson Climate Technologies
234
System Protectors
PCN Description
Connection
Size
Number
Of
100 in
3
Cores
Dimensions (in)
Weight
(lbs)
A B C D F* G
026570 ADKS-30013T 1 5/8 ODF
3
25.27 20.32 5.24 1.13
6.00 7.56
39.00
037978 ADKS-30017T 2 1/8 ODF 25.41 20.45 5.43 1.66
032105 ADKS-40017T 2 1/8 ODF
4
31.91 26.95 5.43 1.66
46.00
037570 ADKS-40021T 2 5/8 ODF 32.81 27.86 6.19 1.47
* Does not include weld bead
1
“H” Dimension is the clearance required to change the internal hardware assembly
T = 1/4” FPT access connection
Specifications
Filtration (with core): 40 microns
Maximum working pressure: 500 psig*
UL/CUL le number: SA 3124
Bolt Torque: 35 ft-lbs
*Note: Not suitable for R-410A applications above 500 psig.
The ADKS is a replaceable core lter drier for use with CFC, HCFC,
and HFC refrigerants in very large commercial air conditioning and
refrigerant systems.
Features
Full ow ttings for low pressure drop
Corrosion resistant epoxy powder paint nish
Sturdy steel shells for long life durability
Nomenclature example: ADKS 30013T
ADKS 300 13 T
System
Protector
Serie
s
Unit Size
(in cu. in.
)
Connection Size
(in 1/8”)
T = Tap Access
Connection
Ordering Information
Dimensional Data
ADKS Models are shipped without lter cores or lter drier
cores. See lter or lter drier cores for availability.
ADKS Liquid and Suction Line Filter Drier