Brochure
Emerson Climate Technologies 
214
Mechanical Pressure Regulators
249
For other evaporating temperatures the bypass capacity Q
Byp
 shall 
be multiplied with the correction factor K
Byp
.
Q
Byp
 x K
Byp
 = Q
n
Q
Byp
:  Required bypass capacity
K
Byp
:  Correction factor for evaporating    
  temperature
Q
n
:  Nominal valve capacity
Correction Tables for Series ACP and CPHE
Refrigerant
Condensing 
Temperature
°C
Correction Factor K
Byp
Evaporating Temperature °C
+10 0 -10 -20 -30 -40
R134a
50 0.78 0.77 0.78 0.80
40 0.99 0.94 0.93 0.94
30 1.35 1.21 1.15 1.14
R22
50 0.80 0.77 0.77 0.77 0.79 0.82
40 1.00 0.93 0.91 0.91 0.92 0.95
30 1.34 1.19 1.12 1.10 1.09 1.12
R407C
50 0.83 0.82 0.83 0.86
40 0.99 0.95 0.95 0.97
30 1.26 1.17 1.13 1.13
R404A / R507
50 0.86 0.85 0.87 0.91 0.97 1.06
40 0.99 0.95 0.94 0.96 1.00 1.05
30 1.26 1.13 1.09 1.08 1.10 1.14
CPHE