Brochure
Emerson Climate Technologies
199
Solenoid Valves & Coils
Ordering Information and Nominal* Liquid Capacity Table – Tons (kW)
PCN
Description
Connection
Size
R-134a R-22 R-407C R-404A/R-507
Standard
Valve
Mounting
Stud
1
Manual
Stem
2
060374 040846 040845 240RA 8 T 5 5/8 ODF
14.8 (52.5) 15.6 (55.2) 14.8 (52.4) 8.4 (29.5)
060375 044860 045753 240RA 8 T 7 7/8 ODF
060376 040848 040847 240RA 9 T 5 5/8 ODF 22.0 (78.0) 23.3 (82.5) 22.1 (78.2) 15.3 (54.2)
060377 043205 043204 240RA 9 T 7 7/8 ODF
28.9 (102.3) 30.5 (108.0) 29.0 (103.0) 21.0 (71.1)
060378 044861 045752 240RA 9 T 9 1 1/8 ODF
060379 040850 040849 240RA 12 T 7 7/8 ODF
33.2 (117.5) 34.9 (124.0) 33.2 (118.0) 23.0 (81.4)
060380 043959 045549 240RA 12 T 9 1 1/8 ODF
060381 042549 042548 240RA 16 T 9 1 1/8 ODF
55.1 (195.1) 58.0 (205.0) 55.2 (195.0) 38.3 (135.0)
060382 044428 044788 240RA 16 T 11 1 3/8 ODF
060383 047761 046636 240RA 20 T 11 1 3/8 ODF
86.8 (307.4) 95.4 (338.0) 90.8 (321.0) 65.7 (230.0)060384 047747 046637 240RA 20 T 13 1 5/8 ODF
060385 054297 046638 240RA 20 T 17 2 1/8 ODF
Features
• Onecoiltsallvalvesizes
• Canbebrazedintothelinewithoutdisassembly
• PTFEdiaphragmforhightemperature
applications
• Extendedendsforeasyinstallation(standard)
• Long-lifemoldedcoils
• Mountingstudmodelscanbeeldconvertedto
manual stem
Specifications
• Maximumuidtemperature: 250°F
• Maximumworkingpressure: 500psig
• MOPD: 300psig
• UL/CULlenumber: MP604
NOTE: Mounting enclosing tube more than 90
o
off vertical up
position is not recommended.
The 240RA is a 2-way, normally closed diaphragm valve. 240RA
valves are used for liquid, suction, and hot gas service.
Options
• Manual stem or mounting stud
1
Add “T” to the end of description for Mounting Stud
2
Add “M” to the end of the description for Manual Stem
Nomenclature
example:240RA8T5MVLC
240R A**
8 T 5 M VLC
Valve
Series
Design
Series
Port Size
(in 1/16”)
Connection Type
T = copper entended ends
Connection Size
(in 1/8”)
M = manual stem
T = mounting stud
(optional)
Coil*
*NOTE:Valvesareshippedwithoutthesolenoidcoils(VLC=ValveLessCoil).Seecoilassembliesforavailability.
**NOTE:Letter“H”isnolongerusedsinceall240RAvalvesnowcontainthehightemperaturediaphragmforhotgas.
Capacities based on 100°F liquid and 40°F saturated evaporator per ARI standard 760-87.
*See Extended Capacity Tables for ratings at a wide range of conditions.
240RA