Brochure
Emerson Climate Technologies
179
EX Extended Capacity Tables
R-404A/R-507 Extended Capacities (kWatts) EX6-8 Series,
Application Suction Pressure Regulation (Evaporating or Crankcase Pressure)
Valve Type
Condensing
Temperature
°C
Evaporating Temperature (°C)
+10 +5 0 -20 -30 -40
EX6
+60
3 2 2 1 1 1
EX7
9 8 8 4 3 2
EX8
29 26 23 13 10 7
EX6
+50
3 3 3 2 1 1
EX7
12 11 9 6 4 3
EX8
36 32 29 18 13 9
EX6
+40
4 3 3 2 1 1
EX7
14 12 11 7 5 4
EX8
42 38 34 21 16 12
EX6
+30
4 4 4 2 2 1
EX7
16 14 13 8 6 5
EX8
48 43 39 25 19 14
EX6
+20
5 4 4 3 2 1
EX7
17 16 14 9 7 5
EX8
53 48 44 28 21 16
R-407C Extended Capacities (kWatts) EX6-8 Series, Application Suction Pressure Regulation
(Evaporating or Crankcase Pressure)
Valve Type
Condensing Temperature
Evaporating Temperature (°C)
Dew point
°C
Bubble point
°C
+10 +5 0 -10 -20
EX6
+64 +60
3 3 3 2 2
EX7
12 11 10 8 6
EX8
36 33 29 23 18
EX6
+54 +50
4 3 3 2 2
EX7
14 12 11 9 7
EX8
41 37 34 27 21
EX6
+45 +40
4 4 3 3 2
EX7
15 14 12 10 8
EX8
46 42 38 30 23
EX6
+35 +30
5 4 4 3 2
EX7
17 15 14 11 9
EX8
51 46 41 33 26
EX6
+26 +20
5 5 4 3 3
EX7
18 16 15 12 9
EX8
55 50 45 36 28