EX Extended Capacity Tables
R-407C Extended Capacities (Tons) - EX5-8 Series,
condensing pressure regulator and liquid duty
Valve Type
Condensing Temperature
Dew Point °F
Evaporating Temperature °F
50 40 30 20
EX5
140
4 4 4 4
EX6
9 9 9 8
EX7
32 32 31 30
EX8
98 96 94 91
EX5
130
4 4 4 4
EX6
10 10 9 9
EX7
35 34 34 33
EX8
106 105 102 100
EX5
120
5 5 4 4
EX6
11 11 10 10
EX7
38 38 37 36
EX8
117 115 112 110
EX5
110
5 5 5 5
EX6
12 11 11 11
EX7
41 40 40 39
EX8
125 123 120 118
EX5
100
5 5 5 5
EX6
12 12 12 12
EX7
44 44 43 42
EX8
135 133 130 128
EX6-8 Nominal capacities (Tons) - for hot gas flow such as heat reclaim application
Valve Type R-22 / R-407C R-404A / R-507
EX6
3.1 2.8
EX7
11.1 10.2
EX8
33.8 30.7
The nominal capacity is based on the following conditions:
Refrigerant Evaporating temperature Condensing temperature Subcooling Pressure Drop Isentropic Efciency
R-22, R-404A, R-507 +40°F +100°F 2°F 2 psid 80%
R-407C +40°F bubble point +100°F dew point 2°F 2 psid 80%
Remarks: Bi-ow versions are not released for hot gas ow applications.
EX6, EX7 and EX8 must be installed with motor downward in suction line applications.
This insures the valve life expectancy.