Product Overview

2004FC-118 R13 (01/14)
Emerson Climate Technologies
TXV 5
Thermal Expansion Valves
AFA Series – Nominal* Capacity Table in Tons (kW)
R-12 R-134a R-22 R-502 R-507/R-404A R-407C
1/8 (0.4) 1/5 (0.7) 1/8 (0.4) 1/5 (0.7)
1/8 (0.4) 1/4 (0.9) 1/4 (0.9) 1/8 (0.4) 1/4 (0.9) 1/4 (0.9)
1/4 (0.9) 1/2 (1.8) 1/2 (1.8) 1/4 (0.9) 1/2 (1.8) 1/2 (1.8)
1/2 (1.8) 3/4 (2.7) 1 (3.5) 1/2 (1.8) 3/4 (2.7) 1 (3.5)
1 (3.5) 1 (3.5) 1½ (5.3) 1 (3.5) 1 (3.5) 1¼ (4.4)
1½ (5.3) 2 (7.0) 1¼ (4.4) 2 (7.0)
1½ (5.3) 2 (7.0) 2½ (9.0) 1½ (5.3) 2 (7.0) 2½ (9.0)
2 (7.0) 2½ (9.0) 3 (11.0) 2 (7.0) 2¼ (8.0) 3¼ (11.5)
3 (11.0) 2½ (9.0) 4 (14.0)
3 (11.0) 4 (14.0) 5 (17.0) 3 (11.0) 3½ (12.0) 5¼ (19.0)
Nomenclature example: AFAE 1/2 HC 5 FT 3/8 x 1/2 SAE ANG
AF A E 1/2 H C 5 FT 3/8 x 1/2 SAE ANG
Valve
Series
Hermetic
Design,
Flare
Connections
Superheat
Adjustment
A = Adjustable
Equalizer
E=External
(Omit for
Internal)
Capacity
Nominal Rating
in Tons
(See nominal
capacity table
below)
Refrigerant Code
+F = R-12
• H = R-22
+M = R-134a
• N = R-407C
*P = R-507
*R = R-502
*S = R-404A
Z = R-410A
Charge Code
C = medium temp
CA = heat pump
W(MOP) = press.
limiting
Z = low temp
AA = wide range
Capillary Tube
Length
30 IN
&
5 FT (std)
Inlet x Outlet
Connection Sizes
1/4 x 3/8
3/8 x 1/2
Connection
Type
SAE=are
Conguration
ANG = 90° angle
Features
Stainless steel power element eliminates corrosion and
prevents valve failure
External superheat adjustment
Replaceable inlet strainer
SAE connections only
Wrench ats on inlet and outlet
AFA(E) Series
The AFA series is designed for air conditioning and commercial
refrigeration applications requiring angle conguration SAE
connections. The AFA is ideal for those applications requiring
compact size combined with stable and accurate control over
wide load and evaporator temperature ranges.
Specifications
Maximum working pressure: 700 psig
UL/CUL le number: SA 5312
Options
External or internal equalizer
Dimensional Data
Remote Bulb Tubing Length 30” or 5’ Standard
All capacities shown are at 100°F condensing, 40°F evaporator temperature.
*See Extended Capacity Tables for ratings at a wide range of conditions per ARI standard 750.
AFA(E) Connections (in)
Inlet Outlet A B C
1/4 SAE
elbow
3/8 SAE
1/2 SAE
5/8 SAE
3/8 – 1/2 SAE
1.56
1.31
1.64
1.35
1.98
1.73
3/8 SAE
elbow
3/8 SAE
1/2 SAE
5/8 SAE
3/8 – 1/2 SAE
1.47
1.34
1.36
1.98
1.73
+ = R-12 and R-134a are interchangeable refrigerant charges, * = R-507, R-502 and R-404A are interchangeable refrigerant charges, • = R-22 and R-407C are interchangeable refrigerant charges
.88

Summary of content (2 pages)