6.0 Power Requirements
Jacuzzi
®
spas are designed to provide optimum performance and
exibility of use when connected to their maximum electrical service.
They are congured at the factory. The most common electrical
connections are listed below:
All North American 60 Hz Models: 240VAC/50A**•
All Export 50 Hz Models: 240VAC/30A**•
If you prefer, your qualied technician can perform a minor circuit board
modication that allows the spas to operate on a different electrical
service (see table footnotes below).
North American J-460/J-465/J-470/J-480 Models (60 Hz)
Voltage: 240VAC 240VAC 240VAC
Max. Current Draw: 23A 36A 45A
Frequency: 60 Hz 60 Hz 60 Hz
Number of Wires: 3 3 3
Circuit Breaker (2-Pole): 30A* 50A** 60A***
*
In 30A conguration, the heater will not operate while either jets
pump is running.
**
In 50A conguration, the heater will not operate while both jets
pumps are running. This is the factory setting.
***
In 60A conguration the heater will operate while both jets pumps
are running.
Export J-460/J-465/J-470/J-480 Models (50 Hz)
Voltage: 240VAC 240VAC 240VAC
Max. Current Draw: 16A 21A 29A
Frequency: 50 Hz 50 Hz 50 Hz
Number of Wires: 3 3 3
Circuit Breaker (2-Pole): 20A* 30A** 40A***
*
In 20A conguration, the heater will not operate while either jets
pump is running.
**
In 30A conguration, the heater will not operate while both jets
pumps are running. This is the factory setting.
***
In 40A conguration the heater will operate while both jets pumps
are running.