User manual
Slave Components - G-Modules (General Purpose)
Product Catalogue all information for reference only - technical changes reserved - rev. 9 Page 53 of 171
6.2.4.6 Technical Data
Note: For further global specification aditionally refer to chapter 4
Outputs:
Number of relays ....................... 3x normal open (NO)
Type ....................................... isolated
Switching voltage (-01) ......... max. 240Vac / 28Vdc
Switching voltage (-02) ......... max. 400Vac / 30Vdc
Contact current (-01) ............. max. 30Aac / 20Adc, for details refer to the T9AS1D datasheet
Contact current (-02) ............. max. 10Aac / 10Adc for details refer to the F4341-24S
datasheet
Permanent load (-01) ............ max. 16 Aac / 16 Adc
Permanent load (-02) ............ max. 6 Aac / 6 Adc
Lifetime ............................... refer to the T9AS1D/ F4341-24S datasheet
Others:
Separate supply voltage ........... 24V DC ±10 % (used for relay supply only)
Bus power consumption ........... 0..150mA@24V, <10mA@3.3V
Status indication ....................... LEDs for each output and for the module status
Mechanics:
Terminals ................................... 6, screw terminals
Connection ................................ usable with one litz wire from 0.5 –6 mm² and AMP
Dimensions .............................. 88 x 72 x 20 mm
Weight ........................................ approx. 100 g
Options:
AMP-6,3 terminals ..................... optional available