User manual

Slave Components - G-Modules (General Purpose)
Product Catalogue all information for reference only - technical changes reserved - rev. 9 Page 65 of 171
6.2.7.3 Terminal Assignment
Circuit Example
Ident.
Ter.
Function
Usage
internal simplified diagram
(lower terminal row)
24V
1
Analog-Input 1
+24V Supply
AI0
2
Input
0V
3
GND
24V
4
Analog-Input 2
+24V Supply
AI1
5
Input
0V
6
GND
24V
7
Analog-Input 3
+24V Supply
AI2
8
Input
0V
9
GND
24V
10
Analog-Input 4
+24V Supply
AI3
11
Input
0V
12
GND
(upper terminal row)
24V
13
Analog-Input 5
+24V Supply
AI4
14
Input
0V
15
GND
24V
16
Impuls Input 1
+24V Supply
I0
17
Input
0V
18
GND
24V
19
Impuls Input 2
+24V Supply
I1
20
Input
0V
21
GND
24V
22
Impuls Input 3
+24V Supply
I2
23
Input
0V
24
GND
6.2.7.4 LED Indications
IMP0..2 ..................................... status indication of the Imp0..2 (only active with -01 + -03)
Status-LED .................................. module status (see 6.1.1)
6.2.7.5 Application Note
In addition to the notes in chapter 4, please regard the following:
The voltage range of the analog inputs (10V variant) can be expanded by an external series
resistor in the input line. Thefore the input resistance of the board is exact 104KOhm, the
external resistor has to be also 104kOhm for every 10V range expansion.
e.g. for a range expansion to 0...50V you have to use a calculated series resistor of 4 x
104kOhm = 416 kOhm (use 390kOhm + 27kOhm of the E12 row). The filter behavior will not
be changed.
250mA Polyfuse