6.5.4.4 LED Indications
Output LED1..6 ............................ status indication of the relays 1…6
Input LED7..11 ............................ status indication of the Inputs
Status-LED .................................. module status (see 6.1.1)
6.5.4.5 Application Note
In addition to the notes in chapter 4, please regard the following:
Make sure that the GND of the analog signals is connected to the 0V terminal. Otherwise
the measurement will loose precision.
The 2 potential-free relays (Relay 5 + 6) have to operate on the same voltage level 230VAC
or 24VAC or 24VDC. A mixture of different voltage levels is not allowed.
Current measurement is only active when one wire (L or N) is carried through the current
sensor only one time.
On the backside of the PCB the contacts are touchable, so you have to keep the PCB in a
housing.
This module support relay contacts. For the two potential free depending on the electrical
application, the user has to install sufficient additional components to fulfill the
EMC-standads and the requirements of the relay producer (see relay datasheet), especially
when driving inductive/capacitive or high inrush current loads. The other four have inbuild
RC-Parts on the Board.