Datasheet

Slave Components
- B-Modules (Building)
Product Catalogue
all information for reference only - technical changes reserved - rev. 11p
Page 94 of 180
6.4.3.6 Technical Data
Outputs:
Number of dimmer outputs....... 4
Connection technology ......... 1-wire (plus separate supply)
for 4-541:
Type ................................... leading edge
Output range ..................... 0..100%
for 4-542:
Type ................................... trailing edge
Output range ..................... 0...100%
Resolution ............................. 10 Bit, 0.1% (related on measure range)
Linearity ................................. 0.2% (related on measure range)
Accuracy ................................ 0.5% (related on measure range)
Filter....................................... hardware, 1
st
order, f
cut off
= approx. 100Hz
Others:
Separate supply voltage ........... 230V 50Hz (used for output supply only)
Bus power consumption ........... sensor supply@24V, <16mA@3.3V
Isolation bus to I/O .................... none (important details: consider to chapter 4)
Status indication ....................... LEDs for each digital input, output and for the module status
Mechanics:
Terminals ................................... 6, cage clamp Wago250
Connection ................................ usable with one litz wire from 0.5 – 1.5 mm²
Dimensions .............................. 88 x 72 x 20 mm
Weight ...................................... approx. 85g