Datasheet
Slave Components
- B-Modules (Building)
Product Catalogue
all information for reference only - technical changes reserved - rev. 11p
Page 93 of 180
6.4.3.3 Terminal Assignment
Circuit Example Ident.
Ter.
Function Usage internal simplified diagram
N
1
Supply Input AC
Null
-
Phase
L
2
Aktiv
-
Phase
LO
1
3
Dimmer
1
Output
LO
2
4
Dim
mer
2
Output
LO
3
5
D
immer
3
Output
LO
4
6
Dimmer
4
Output
6.4.3.4 LED Indications
Output LED1..4 ............................ status indication of the outputs
Status-LED .................................. module status (see 6.1.1)
6.4.3.5 Application Note
In addition to the notes in chapter 4, please regard the following:
๎ To save a secure usement each output is fused with quick reacting 1.6A.
๎ The module does not contain any output inductors. For common use, this results in fol-
lowing IMPORTANT application requirements else a destruction of the module is very like-
ly):
a) for resistive loads use trailing edge mode. A separate inductor is NOT necessary.
b) for capactive loads use trailing edge mode. A separate inductor is NOT necessary.
c) for inductive loads use leading edge mode and an inline inductor of > 1mH
๎ For high level application (medical, stage equipment, ...) we recommend an inline inductor
in all operation cases that limits the current increase (tau) to 50 ... 500ยตs.
M
F
2
A
AC/DC