6.4.5.7 Process Datae Image
Organisation of the user data communicated via brickBUS:
Out-Userdata from Master to Slave
total: 8 Bytes
In-Userdata to Master from Slave
total: 8 Bytes
Byte
Function
rC Assign...
Byte
Function
rC Assign...
0, 1
Dimmer 1
0...24000 Dig. 0..100%
... + eB_W0, 0, ...
0, 1
State-Dimmer 1
... + eB_W0, 0, ...
2, 3
Dimmer 2
0...24000 Dig. 0..100%
... + eB_W1, 0, ...
2, 3
State-Dimmer 2
... + eB_W1, 0, ...
4, 5
Dimmer 3
0...24000 Dig. 0..100%
... + eB_W2, 0, ...
4, 5
State-Dimmer 3
... + eB_W2, 0, ...
6, 7
Dimmer 4
0...24000 Dig. 0..100%
... + eB_W3, 0, ...
6, 7
State-Dimmer 4
... + eB_W3, 0, ...
Analog Output x
AOV15
AOV14
AOV13
AOV12
AOV11
AOV10
AOV9
AOV8
Bit 15
Bit 8
AOV7
AOV6
AOV5
AOV4
AOV3
AOV2
AOV1
AOV0
Bit 7
Bit 0
Bit 15-0 ....................................... AOV<15:0>: Analog Output Value (Little Endian)
101 1101 1100 0000 = 24000 (output PWM with 100%)
000 0000 0000 0000 =0 (output PWM with 0%)
6.4.5.8 Programming Note
In addition to the notes in chapter 4, please regard the following:
State-Dimmer is functional at the moment