User manual
Slave Components - G-Modules (General Purpose)
Product Catalogue all information for reference only - technical changes reserved - rev. 9 Page 49 of 171
6.2.3.6 Technical Data
Note: For further global specifications refer to chapter 4
Outputs:
Number of Relays NO ................ 2 (normal open, each with 2 terminals)
Number of Relays CO ................ 4 (change over, each with 3 terminal)
Type ....................................... isolated
Switching voltage.................. max. 230Vac / 24Vdc
Switching current .................. max. 6A ac/dc, for details refer to the LYCA024V datasheet.
The terminal blocks rated VDE 250V/3A, UL 300V/6A. The user
have to install an appropriate fuse in the supply line of the re-
lays.
Permanent load ..................... max. 4 Aac/dc
Lifetime.................................. refer to the LYCA024V datasheet
Others:
Separate supply voltage ........... 24V DC ±10 % (by brickBUS, used for relay supply only)
Bus power consumption ........... 0..50mA@24V, <10mA@3.3V
Status indication ....................... LEDs for each output and for the module status
Mechanics:
Terminals ................................... 4 + 12, cage clamp Wago250
Connection ................................ usable with one litz wire from 0.2 – 1.5 mm²
Dimensions .............................. 66 x 72 x 20 mm
Weight ........................................ approx. 60 g