User manual

Slave Components - G-Modules (General Purpose)
Product Catalogue all information for reference only - technical changes reserved - rev. 9 Page 48 of 171
6.2.3.3 Terminal Assignment
Circuit Example
Ident.
Ter.
Function
Usage
internal simplified diagram
CO
1
Relay 1
change-over
NO
2
normally-open
CO
3
Relay 2
change-over
NO
4
normally-open
NC
5
Relay 3
normally-closed
CO
6
change-over
NO
7
normally-open
NC
8
Relay 4
normally-closed
CO
9
change-over
NO
10
normally-open
NC
11
Relay 5
normally-closed
CO
12
change-over
NO
13
normally-open
NC
14
Relay 6
normally-closed
CO
15
change-over
NO
16
normally-open
6.2.3.4 LED Indications
Output-LED1..6 .......................... status indication of the output Relays 1..6
Status-LED .................................. module status (see 6.1.1)
6.2.3.5 Application Note
In Addition to the notes in chapter 4, please regard the following:
All six relay have to operate on the same voltage level 230VAC or 24VAC or 24VDC. A mix-
ture of different voltage levels is not allowed.
The user have to install an appropriate fuse in the lines concerning the technical data be-
low.
This module support relay contacts. Depending on the electrical application, the user has
to install sufficient additional components to fulfill the EMC-standads and the require-
ments of the relay producer (see relay datasheet), especially when driving induc-
tive/capacitive or high inrush current loads.