5.3.1.8 Technical Data
Inputs/Outputs:
Supply ........................................ 24Vdc
Ethernet ..................................... 10/100MBit, 1kV islolated, RJ45
CAN ............................................ 2.0B, max. 1MBit, Molex-KK
RS485 ........................................ max. 1 MBit, not isolated, cage clamps
RS232 ........................................ max. 115 kBit, not isolated, pin connector
General:
own power supply
for emBRICK usage ........... 24 Vdc, ±10 %, via K7
for general usage ................ 12…24 Vdc, ±10 %, via K7
supply current
own, with LAN ..................... approx. 43mA@24V
own, with WLAN .................. approx. 105mA@24V
with external loads ............ <1.0 A
output supply capability............ nominal: 0,75A@24V, 0,5A@3.3V
Status indication ....................... via 3 status LEDs
Mechanical Data:
Size (WxHxD) ........................... 121 x 72 x 20 mm
Wight .......................................... approx. 60 g
Terminals ................................... cage clamp Wago250, RJ45, Molex KK
brickBUS:
Supported speed level ............... BBS1
5.3.1.9 Process Data Image
Out-Userdata from remote-master to lo-
cal-master
total: 3 Bytes
In-Userdata to remote-master from local-master
total: 2 Bytes
Byte
Function
rC Assign...
Byte
Function
rC Assign...
0
Control Bits
Bit 0 = clear EEPROM Error
Bit 1 = reinitialize BUS
Bit 2 = pause BUS
... + eB_B0, 0, ...
0
Control Flags
Bit 0 = EEPROM Error
Bit 1 = communication error
... + eB_W0, 0, ...
2
Set expected Size of Bus
0..31 (0 = function disabled)
... + eB_B2, 0, ...
1
Actual size of BUS
... + eB_W1, 0, ...
5.3.1.10 RS485 used as an expanded IO-Port
In TCP/IP mode, the RS485-Interface can be used as an additional IO interface for the coupling
and support of serial data devices. Further information on request.