Installation Guide
ON
POSITION
OFF
POSITION
GRH/OV 020MANUAL SHUT-OFF VALVE
Figure 6 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff
Valve
PRESSURE TESTING APPLIANCE
GAS CONNECTIONS
1. Open equipment shutoff valve (see Figure 6).
2. For natural gas, open main gas valve located on or near
gas meter. For propane/LP gas, open propane/LP supply
tank valve.
3. Make sure control knob of fireplace is in the OFF posi-
tion.
4. Check all joints from equipment shutoff valve to gas
control valve. Apply noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fireplace (see Operating Log Set, page 14). Check
all other internal joints for leaks.
7. Turn off fireplace (see To Turn Off Gas To Log Set, page
14).
INSTALLATION
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 6).
2. Pressurize supply piping system by either opening
propane/LP supply tank valve for propane/LP gas or
opening main gas valve located on or near gas meter of
natural gas or using compressed air.
3. Check all joints from gas meter to equipment shutoff
valve for natural gas or propane/LP supply to equipment
shutoff valve for propane/LP. Apply
noncorrosive leak
detection fluid to all joints. Bubbles forming show a
leak.
4. Correct all leaks at once.
CONTINUED
10
INSTALLATION OF
DECORATIVE LOGS
Diagrams are provided on the following pages (page
11 thru 13) for the proper positioning of the provided
decorative gas logs.
Carefully follow the instruction that is provided for
the model you are installing.
We recommend that each log be positioned on the
grate carefully, and that the installer ensure the
cut-outs in the bottom of the logs fit over the feat-
ures of the grate they mate with.
Use only the logs provided. Do not add items not inc-
luded with this set.
When operating, the burner flames should not be imp-
inging on (touching) any of the logs. Improperly
placed logs (logs impinging the flame) can cause
excessive carbon build-up (sooting) and poor combust-
ion.
to use only parts specificly approved for
WARNING: Failure to position the parts in
accordance with these diagrams or failure
this heater may result in property damage
or personal injury.