Installation Guide
ON
POSITION
OFF
POSITION
Figure 6 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff
Valve
PRESSURE TESTING APPLIANCE
GAS CONNECTIONS
1. Open equipment shutoff valve (see Figure 14).
2. For natural gas, open main gas valve located on or near
gas meter. For propane/LP gas, open propane/LP supply
tank valve.
3. Make sure control knob of is in the OFF posi-
tion.
4. Check all joints from equipment shutoff valve to gas
control valve. Apply noncorrosive leak detection
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light replace (see Operating Log Set, page 13). Check
all other internal joints for leaks.
7. Turn off eplace (see To Turn Off Gas To Log Set, page
14).
INSTALLATION
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 6).
2. Pressurize supply piping system by either opening
propane/LP supply tank valve for propane/LP gas or
opening main gas valve located on or near gas meter of
natural gas or using compressed air.
3. Check all joints from gas meter to equipment shutoff
valve for natural gas or propane/LP supply to equipment
shutoff valve for propane/LP. Apply noncorrosive leak
detection to all joints. Bubbles forming show a
leak.
4. Correct all leaks at once.
CONTINUED
10