Product data
42
VMEbus
MEN VMEbus
Binary I/Os
■ 128 binary signals
■■ 4 optically isolated units, 32 channels for each unit
■ Individual use of each channel as input or output
■ Individual edge-triggered interrupts
■ Input/output load on ground
■ High-side output switches
■ High output current
■■ Max. 1.9A per channel, max. 16A per unit
■ Over-current and over-temperature protection
Output Characteristics
■ Output voltage range: 12V..32V
■ Output current log. 0: max. 10mA
■ Output current log. 1: max. 1.9A
■ Switching time for output change: < 200µs
■ Isolation voltage (optocoupler): 500V DC
Input Characteristics
■ Input voltage min.: 0V
■ Input voltage max. external supply voltage (12..32V)
■ Voltage level log. 0: 0V..6V or open
■ Voltage level log. 1: 12V..32V
■ Input current log. 1: 2.03mA @ 24V
■ Switching threshold: 9.2V @ 0.78mA typ.
■ Switching time for input change: min. 33µs, max. 44µs
■ Excess voltage protection: max. +47V
■ 1-slot A24/D16 VMEbus slave
■ 4 optically isolated units with 32 channels for each unit
■ Individual use of each channel as input or output
■ Individual edge-triggered interrupts
■ Input/output load on ground
■ High-side output switches
■ High output current: max. 1.9A per channel or 16A per unit
■ Over-current and over-temperature protection
The A201S is an M-Module carrier board for universal I/O
on the VMEbus, allowing high flexibility in applications
such as process and motion control, measuring and instru-
mentation, communication or special-purpose tasks. The
M-Modules are screwed tightly on the carrier board, but
the board needs only one slot on the VMEbus. An interrupt
controller handles the M-Modules individually. In VMEbus
D16 systems the I/O signals of the M-Modules can be
accessed from P2/J2 inside the rack.
■ 4 M-Module slots
■ 1 VMEbus slot
■ VMEbus slave A16/A24/D16,
interrupter
A302 – 6U VMEbus Card with 128 Binary I/Os
A201S – 6U VMEbus Carrier
Board for M-Modules