TROUBLESHOOTING
Problem
Indcaton
Probable Cause
Remedy
Poor Dewpont
n/a
Hgh nlet temperature
Check after cooler condton and clean
as necessary
Entraned Water
Check pre-fltraton and pre-fltraton
drans
Excessve ar flow
demand
Check actual flow aganst rated flow of
dryer
Check for recent addtons to ar
system
Inlet pressure too low
Check aganst techncal specfcaton
Excessve nlet ar
temperature
Check aganst techncal specfcaton
Insuffcent purge ar flow
Factory set for 100 psg system
pressure
Exhaust slencers
blocked
Change by traned personnel
Contamnated desccant
Elmnate source of contamnaton.
Desccant change by
traned personnel
Electrcal Fault
Power LED ‘OFF’
Hardware fault
Contact customer servce
Falure to Purge
No depressursaton
and poor dewpont
Purge valve blocked or
shut
Traned personnel to adjust
Exhaust slencer blocked
Change by traned personnel
Outlet Ar Flow Stops
Downstream
pressure drops
No ar suply to the dryer
Check compressor ar supply to dryer
Check all ppework and fttngs for
leaks
Constant
depressursaton
Erratc ar flow from
exhaust
Damaged valve
Change by traned personnel