User manual

DC Controller
UPC4 Master
User Manual
Page 73/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
Token (UPC4 commands)
%m Sending without \r\n and waiting for answer from the modem
%d 1 s pause
%p 0.25 s pause
%t40 Timeout 40 s Default 5 s (1-99 s)
%t Timeout 320 ms min = 320 ms
%t0 ditto
%t100 ditto
%t400 Timeout 400 ms 320 .. 999 ms
%O Waiting for OK\r\n modem message
%C Waiting for CONNECT\r\n ditto
%0 Waiting without check Default
%% results in % as normal character
Communication operation of the strin
g AT AT%O AT&F %dATX3E0L1S0=0
(/r/n = carriage return line feed)
Explanation of the AT commands:
AT
&F= Factory setting
X3= Do not wait for dial tone
E0= 0 Deactivates echo of sent bytes
L1= Loudspeaker active, sound level 1
S0=0 Modem answers not self acting
At section 5.3.4 Operating status „Modem“
the status of the modem is shown.
6.10.7 Fieldbus*
(* requires 9.10 ), see section 6.4.2.
As fieldbus currently Modbus or (probably
in the near f
uture) ProfiBus can be enabled
at Service/Enable
.
The slave address of Modbus or ProfiBus
resp
ectively can be set at (31.1)
*9.10
.
Modbus parameters
These parameters are only relevant for Modbus operation. Serial settings such as parity (31.2)
*9.10
,
baudrate (31.3)
*9.10
, and mode (31.4)
*9.10
have to be set accordingly.
31.1
31.2
31.3
31.4