Specifications
58
Table 21 — Operating Mode Display Menu
Table 22 — Alarm Menu
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENTS
MODE
MODE MODE Modes Controlling Unit
COOL COOL Cool Mode Cooling Mode in effect
HEAT HEAT Heat Mode Heating Mode in effect
VENT VENT Vent Mode Unit is between heating and cooling mode limits
TMPR TMPR Supply Air Tempering
OCC OCC Currently Occupied unit in occupied mode
T.OVR T.OVR Timed Override in Effect unit operating under timed override
A.DCV A.DCV DCV Resetting Min Pos DCV resetting economizer position
SAT.R SAT.R Supply air Reset supply air reset being used
DMD.L DMD.L Demand Limit in Effect unit being demand limited
T.C.ST TCST Temp. Compensated Start Temp compensated start being used
IAQ.P IAQ.P IAQ Pre-Occ Purge Active IAQ pre-purge
F.CL F.CL Unocc Econ Free Cooling unoccupied economizer free cooling
F.SD F.SD Fire Shutdown fire shutdown
PRES PRES Pressurization fire pressurization — supply fan on, economizer closed, exhaust off
EVAC EVAC Evacuation fire evacuation — exhaust on, economizer open, supply fan off
SMK.P SMK.P Smoke Purge fire smoke purge — supply fan on, exhaust fan on, economizer open
STAT STAT Thermostat Control Thermostat control
LINK LINK Linkage Active - DAV DAV control
TEST TEST Test Mode Active test mode active
FS.OV FS.OV Fire Speed Override fire speed setting being used to control supply fan and inverter
SUBMODE
KEYPAD
ENTRY
DISPLAY ITEM EXPANSION COMMENTS
CURR AXXX, PXXX, or TXXX Current Active Alarms
Alarms are shown as AXXX
Alerts are shown as TXXX,
Pre-Alert shown as PXXX
R.CURR YES/NO Reset All current Alarms Resets current alarms
HIST AXXX, PXXX, or TXXX Alarm History
Alarms are shown as AXXX
Alerts are shown as TXXX,
Pre-Alert shown as PXXX
R.HIS YES/NO Reset Alarm History Clears alarm history
ENTER
ENTER
ENTER
ENTER
ENTER