Specifications
49
Table 19 — Configuration Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
DISP
Display Configuration
METR TEXT — — OFF OFF ON/OFF Metric Display enable metric unit display DISPLAY DISPUNIT
LANG TEXT — — ENGLISH ENGLISH
ENGLISH,
SPANISH, FRENCH,
PORTUGUESE
Language Select Only English at this time DISPLAY LANGUAGE
PROT TEXT — — ENBL ENBL ENBL/DSBL Password Enable enable/disable password protection DISPLAY PASS_EBL
PSWD XXXX — — 1111 1111 0 TO 9999
Password Protection Must
be disabled to change
Password
enter password DISPLAY PASSWORD
TEST TEXT — — OFF OFF ON/OFF Test Display LEDs used to check the operation of the display segments DISPLAY DISPTEST
SW.LG
SW.LG Switch Logic NO/NC No= normally open, NC=normally closed
DM.1.L TEXT OPEN OPEN OPEN/CLSE DMD.LMT.SW.1 Normally:
unpower status configuration of demand limit
switch 1
DISLOGIC DMD_SW1L
DM.2.L TEXT OPEN OPEN OPEN/CLSE DMD.LMT.SW.2 Normally:
unpower status configuration of demand limit
switch 2
DISLOGIC DMD_SW2L
EC.SL TEXT OPEN OPEN OPEN/CLSE Economiz Switch Normally:
unpower status configuration of remote economizer
enable switch
DISLOGIC ECOSWLOG
EVC.L TEXT OPEN OPEN OPEN/CLSE Evacuation SW Normally:
unpower status configuration of fire evacuation
switch
DISLOGIC EVACLOGC
FTS.L TEXT OPEN OPEN OPEN/CLSE Filter Status Normally: unpower status configuration of filter status switch DISLOGIC FLTSLOGC
FSD.L TEXT OPEN OPEN OPEN/CLSE Fire Shutdown Normally: unpower status configuration of fire shutdown switch DISLOGIC FSDLOGIC
IAQ.L TEXT OPEN OPEN OPEN/CLSE IAQ Disc. Input Normally: unpower status configuration of IAQ override switch DISLOGIC IAQINLOG
PRS.L TEXT OPEN OPEN OPEN/CLSE Press. Switch Normally:
unpower status configuration of fire pressurization
switch
DISLOGIC PRESLOGC
PRG.L TEXT OPEN OPEN OPEN/CLSE Smoke Purge SW. Normally: unpower status configuration of fire purge switch DISLOGIC PURGLOGC
PMI.L TEXT OPEN OPEN OPEN/CLSE Remote Switch Normally:
unpower status configuration of remote
control switch
DISLOGIC RMTINLOG
SFS.L TEXT OPEN OPEN OPEN/CLSE Fan Status SW. Normally:
unpower status configuration of fan status pressure
switch
DISLOGIC SFSLOGIC
ENTER