Specifications
47
Table 19 — Configuration Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
OPTS
OPTS Option Sensor Config Option sensor configurations
EDT.R TEXT — — DSBL DSBL ENBL/DSBL EDT Reset Input enable remote reset signal feature UNIT EDTRSENS
ECO.S X — — NONE NONE
0 = NONE,
1 = ECON ENABLE,
2 = POSITION OVERRIDE
Economizer Switch
Used to configure the use of an economizer switch
and how it will be used
UNIT ECOSWCFG
FLS.E TEXT — — DSBL DSBL ENBL/DSBL Filter Stat.SW. Enabled? enable remote filter status switch use
FLTSWORK,
UNIT
FLTS_ENA
SPT.S TEXT — — DSPL DSPL ENBL/DSBL Space Temp Sensor enable use of T55, T56, T58 sensor UNIT SPTSENS
STO.S TEXT — — DSPL DSPL ENBL/DSBL Space Temp Offset Enable the use of T56 sensor offset feature UNIT SPTOSENS
STO.R X F C 5 5 1 TO 10 SPT Offset Range (+/-) range for Offset feature adjustment UNIT SPTO_RNG
R.RH.S TEXT — — DSBL DSBL ENBL/DSBL Return Air RH Sensor enable the use of the return air humidity sensor
ENTHALPY,
UNIT
RARHSENS
O.RH.S TEXT — — DSBL DSBL ENBL/DSBL Outside Air RH Sensor enable the use of an outside air humidity sensor
ENTHALPY,
UNIT
OARHSENS
DMT.S TEXT — — DSBL DSBL ENBL/DSBL Demand Limit Input enable the use of demand limit switch inputs
UNIT,
DMDLIMIT
DEMLSENS
RMT.C X — — NONE NONE
0 = NONE,
1 = OCCUPANCY,
2 = START STOP
Remote Switch Config
Used to configure the remote control switch and
how it will be used
SCHEDOVR RMTINCFG
CMF.D
TEXT Comfort Demand Config Demand Control Setpoints
LC.ON XXX.X F C 1.5 1.5 -1 TO 2.0 DMD Level Lo Cool On Used for Demand Driven Control Logic CDMD_CFG DMDLCON
LC.OF XXX.X F C 1 1 0.5 TO 2.0 DMD Level (-) Lo Cool Off Used for Demand Driven Control Logic CDMD_CFG DMDLCOFF
HC.ON XXX.X F C 0.5 0.5 0.5 TO 2.0 DMD Level(+) Hi Cool On Used for Demand Driven Control Logic CDMD_CFG DMDHCON
LH.ON XXX.X F C 1.5 1.5 -1 TO 2.0 DMD Level Lo Heat On Used for Demand Driven Control Logic CDMD_CFG DMDLHON
LH.OF XXX.X F C 1 1 0.5 TO 2.0 DMD Level (-) Low Heat Off Used for Demand Driven Control Logic CDMD_CFG DMDLHOFF
HH.ON XXX.X F C 0.5 0.5 0.5 TO 2.0 DMD Level (+) Hi Heat On Used for Demand Driven Control Logic CDMD_CFG DMDHHON
CT.LV XXX.X F C 0.1 0.1 0.1 TO 5 Cool Trend Demand Level Trend Temperature adjustment for demand cooling COOL_CFG CTRENDLV
CT.TM XX sec sec 60 60 30 TO 600 Cool Trend Time (secs) Trend time adjustment for demand cooling COOL_CFG CTRENDTM
HT.LV XXX.X F C 0.1 0.1 0.1 TO 5 Heat Trend Demand Level Trend Temperature adjustment for demand heating HEAT_CFG HTRENDLV
HT.TM XX sec sec 60 60 30 TO 600 Heat Trend Time (sec) Trend time adjustment for demand heating HEAT_CFG HTRENDTM
RST
RST Supply Air Reset Config Supply air reset configurations
RST.T X — — NONE NONE
0 = NO RESET,
1 = SPT RESET,
2 = RAT RESET,
3 = 3RD PART RESET
Supply Air Reset Type Configure the type of supply air reset SET_PNT SARSTCFG
RTIO X.X — — 3 3 0.0 TO 10.0 Reset Ratio Used for supply air reset control SET_PNT RTIO
R.LIM XX.X F C 10 10 0 TO 20.0 Reset Limit used for supply air reset control SET_PNT LIMT
ENTER
ENTER
ENTER