Specifications

46
Table 19 — Configuration Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
IAQ
IAQ Configuration Demand Ventilation Configuration
IA.CF X 0 0
0 = NO IAQ, 1 = DCV,
2 = OVERRIDE IAQ,
3 = CNTL MIN POS,
4=MINPOSPOT.
IAQ MinPos Sensor Config Used to configure the use of IAQ control
AIR_QLTY,
AIRQUALT
IAQANCFG
IA.FN X 0 0
0 = NEVER,
1 = OCCUPIED,
2 = OVERRIDE IAQ
IAQ 4-20 ma Fan Config
Used to configure IAQ fan control when using
the4-20mainput
AIR_QLTY,
AIRQUALT,
ECONMIN
IAQANFAN
IA.I.C X 0 0
0=NOIAQ,
1 = DCV,
2 = OVERRIDE IAQ
IAQ Discrete Input Config Used to configure IAQ discrete input
AIR_QLTY,
AIRQUALT,
ECONMIN
IAQINCFG
IA.I.F X 0 0
0 = NEVER,
1 = OCCUPIED,
2 = ALWAYS
IAQ Disc.In Fan Config
Used to configure fan control when using the IAQ
discrete fan input
AIR_QLTY,
AIRQUALT,
ECONMIN
IAQINFAN
AQ.MP XXX % % 0 0 0 TO 100 IAQ Demand Vent Min Pos. minimum position when IAQ below limit
BLDGPRES,
ECONWORK,
SET_PNT,
AIRQUALT,
ECONMIN
IAQMINP
MIN.I XXX % % 20 20 0 TO 100 Economizer Min Position
Economizer minimum occupied position, reference
valve should be set in setpoint screen
BLDGPRES,
ECONWORK,
SET_PNT,
AIRQUALT,
ECONMIN
ECONOMIN
PRG.E TEXT DSBL DSBL ENBL/DSBL IAQ Purge used to enable pre-occupancy purge
CONFIG,
AIRQUALT
PURGEN
PRG.D XX MIN MIN 5 5 5 TO 60 IAQ Purge Duration This is "howlongdowepurge." CONFIG IQPD
PG.LT XXX % % 10 10 0 TO 100 IAQ Purge LOTemp Min Pos low limit on damper position during purge SET_PNT LTMP
PG.HT XXX % % 35 35 0 TO 100 IAQ Purge HITemp Min Pos high limit on damper position during purge SET_PNT HTMP
OVR.P XXX % % 100 100 0 TO 100 IAQ Econo Override Pos position of damper when override is in effect
AIR_QLTY,
AIRQUALT,
ECONMIN
IAQOVPOS
OA.CF X No OAQ No OAQ
0 = NO OAQ,
1 = DCV OAQ,
2=LOKOUT
OAQ 4-20ma Sensor Config Used to configure OAQ sensor
AIR_ALTY,
AIRQUALT,
ECONMIN
OAQANCFG
OAQ.U XXXX 400 400 400-2000 User-Configured OAQ
Used to set the reference level for OAQ when there
is no OAQ sensor. Should be base on a locally mea-
sured value and is typically around 450-550
AIR_QLTY OAQ_MEAS
OAQ.L XXXX ppm ppm 0 0 0 TO 2000 OAQ Lockout Value
above this outside air ppm level the dampers will be
closed to the min IAQ position
AIR_QLTY,
ECONMIN
OAQLOCK
AQD.L XXXX ppm ppm 100 100 0 TO 1000 Diff.Air Quality LOLimit
ppm level above outside air reference for minimum
setting of the IAQ curve
AIR_QLTY,
ECONMIN
DAQ_LOW
AQD.H XXXX ppm ppm 700 700 100 TO 2000 Diff.Air Quality HiLimit
ppm level above outside air reference for maximum
setting of the IAQ curve
AIR_QLTY,
ECONMIN
DAQ_HIGH
DF.ON XXX ppm ppm 400 400 0 TO 2000 DAQ PPM Fan On Setpoint used to control indoor fan on at ppm level ECONMIN FAQFNON
DF.OF XXX ppm ppm 200 200 0 TO 2000 DAQ PPM Fan Off Setpoint used to control indoor fan off at ppm level
AIR_QLTY,
ECONMIN
DAQFNOFF
I.4M XXXX ppm ppm 0 0 0 TO 5000 IAQ Low Reference
used with remoted 4-20ma IAQ and is the ppm level
at 4 ma
SENSWORK,
AIRQUALT,
ECONMIN
IAQREFL
I.20M XXXX ppm ppm 2000 2000 0 TO 5000 IAQ High Reference
used with remote 4-20ma IAQ and is the ppm level
at 20 ma
SENSWORK,
AIRQUALT,
ECONMIN
IAQREFH
O.4M XXXX ppm ppm 0 0 0 TO 5000 OAQ Low Reference
used with remoted 4-20ma OAQ and is the ppm
level at 4 ma
SENSWORK,
AIRQUALT,
ECONMIN
IAQREFL
O.20M XXXX ppm ppm 2000 2000 0 TO 5000 OAQ High Reference
used with remote 4-20ma OAQ and is the ppm level
at 20 ma
SENSWORK,
AIRQUALT,
ECONMIN
IAQREFH
I.CRV XXX ppm ppm 0 0 -5.0 to 5.0 Diff.IAQ Responsiveness IAQ control curve responsiveness setting
AIR_QLTY,
ECONMIN
IAQREACT
ENTER