Specifications
45
Table 19 — Configuration Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
SVFD
SVFD SF VFD Parameters
SP.S TEXT DSBL ENBL ENBL/DSBL Duct Static Pressure Sensor
Enables and disables the use of a supply duct
pressure sensor
UNIT SPSENS
SP.C X — — none VFD Control
1 = NONE,
2 = VFD CONTROL
Static Pressure Control
Enables to use of VFD control for building pressure
control. Only applies to VAV
CONFIG STATICFG
SF.MN XXX % % 20 20 20 TO 40% IDF VFD Minimum Speed
minimum VFD speed, do not set on inverters which
must be set to 0
SFANVFD SVFD_MIN
SF.MX XXX % % 100 100 50 TO 100 IDF VFD Maximum Speed maximum VFD speed SFANVFD SVFD_MAX
SF.FS XXX % % 100 100 0 T0 100 IDF Speed In Fire Mode VFD speed in fire modes SFANVFD SVFD_FSD
SP.KP XX.X — — 20 20 0.0 TO 100.0 Prop. Gain SF VFD
Control Loop Proportional Gain Factor (do not
change)
SFANVFD SPKP
SP.KD X.X — — 0 0 0 TO 50.0 Diff. Gain SF VFD
Control Loop Differential Gain Factor (do not
change)
SFANVFD SPKD
SP.KI X.X — — 2 2 0.0 TO 50.0 Integral Gain SF VFD Control Loop Integral Gain Factor (do not change) SFANVFD SPKI
SP.K X.X — — 1 1 0.0 TO 50.0 System /gain SF VFD Control Loop gain Factor (do not change) SFANVFD SPK
SP.DT XX sec sec 2 2 1 TO 200 VFD PID Time (Seconds) Control Loop PID time Factor (do not change) SFANVFD VFD_TIME
SP.H.L X.XX in-H2O cm-H2O 5 5 -10.0 TO 10.0 Duct Press Sensor HI end used to set upper range on the supply duct pressure
SENSWORK,
SENSCNFG
SP_HIGH
SP.L.L X.XX in-H2O cm-H2O 0 0 -10.0 TO 10.0 Duct Press Sensor Lo end
used to set the lower range on the supply duct
pressure
SENSWORK,
SENSCNFG
SP_LOW
BP
Building Pressure Params Building pressure control configurations
BP.SL X — — 2 2 1,2,3 Modulating PE Alg Select 1,2,3 use routine 2 (do not change) BP_CNTL BPSELECT
BP.S TEXT — — DSBL DSBL ENBL/DSBL Building Pressure Sensor enables the use of the building pressure sensor UNIT BPSENS
BP.R X.XX in-H2O cm-H2O 0.25 0.25 0 TO 1 Bldg Press (+/–) Range use to set range of sensor (+/– limit)
SENSWORK,
SENSCNFG
BP_RANGE
BP.ZG XX.X — — 1 1 0.1 TO 10 BP Threshold Adjustment Threshold adjustment (do not change) BP_CNTL BPZ_GAIN
BP.DT XX MIN 1 1 1 TO 10 BP PID Evaluation PID factor (do not change) BP_CNTL BPPERIOD
BP.HP X.XXX in-H2O cm-H2O 0.05 0.05 0 TO 1.0 High BP Level
Building Pressure Upper Differential limit
(use with routine 2)
BP_CNTL BPHPLVL
BP.LP X.XXX in-H2O cm-H2O 0.04 0.04 0 TO 1.0 Low BP Level
Building Pressure Lower Differential limit
(use with routine 2)
BP_CNTL BPLPLVL