Specifications

43
Table 19 — Configuration Display Menu (cont)
*Size default value is dependent on the size of the unit.
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
HEAT Heating Configurations Gas and Electric Heating Configurations
HT.TY X NO HEAT NO HEAT
0=NOHEAT,
1 = ELECTRIC,
2 = 2-STAGE GAS
3=STAGEDGAS
Heat Type (0,1,2,3) Used to select the type of heating HEAT_CFG HEATTYPE
N.HST X 2 STAGE 2 STAGE
0=2STAGE,
1=5STAGE,
2=7STAGE,
3=9STAGE,
4=11STAGE
Heat Stage Type
Used only for staged gas heat and selects the
sequence that will be used
HEAT_CFG HTSTGTYP
OCC.H TEXT NO NO NO/YES Occupied Heating Enabled Enables occupied heating for VAV
H EATSTAT,
HEAT_CFG,
CONFIG
HTOCCENA
LAT.M TEXT NO NO NO/YES SAT Sensor Sense Heat
Yes = EDT sensor relocated to leaving ductwork
which in needed for Linkage heat monitoring
H E ATSTAT H TLAT MON
E.FOD XX SEC SEC 30 30 10 TO 600 Fan-Off Delay, Elec Heat delay in turning off fans for electric heat HEAT_CFG ELEC_FOD
G.FOD XX SEC SEC 45 45 45 TO 600 Fan-Off Delay, Gas heat delay in turning off fans for gas heat HEAT_CFG GAS_FOD
H.T.CF XX MIN MIN 0 0 0 TO 60 TCST Heat Time/Temp Fact
Used for temperature compensated start in the
heat mode and the prestart time prior to
occupancy is calculated by Time = TCST time -
Kheat *(ohsp - space temp). 0 Disables the
function
CONFIG KHEAT
S.CP.M XX.X % % 45 45 5 TO 45 Max Cap Change Per Cycle
Max % capacity that can be added/removed at
any time. for staged heat control
H E ATSTAT H TCAP MA X
S.PI.R XX 90 90 60 TO 300 PID Algorithm Rate Staged gas, normally should not be changed HEATSTAT HTSGPIDR
S.RIS XX 90 90 60 TO 300 PID algorithm rate Staged Gas rise clamp HEATSTAT HTSGPIDR
S.MR.D X.X 0.5 0.5 0 TO 5.0 S. Gas DB Min. dF/PID Rate PID rate of change factor HEATSTAT HT_MR_DB
S.DB X.X F F 2 2 0 TO 5.0 ST.Gas Temp. Dead Band Deadband where changes will not be made HEATSTAT HT_SG_DB
S.P.GN X.X 1 1 0 TO 1.5 Proportional Gain PID proportional gain factor HEATSTAT HT_PGAIN
S.I.GN X.X 1 1 0 TO 1.5 Integral Gain PID integral gain factor HEATSTAT HT_IGAIN
S.DGN X.X 1 1 0 TO 1.5 Derivative Gain PID derivative gain factor HEATSTAT HT_DGAIN
TMPR TMPR Temperature Configurations VAV Tempering configurations
T.CL XX F C 40 40 -20 TO 40.0 Tempering in Cool SASP
SASP = Supply Air Setpoint while cooling in
tempering mode
SET_PNT TEMPCOOL
T.VO XX F C 65 65 -20 TO 80 Tempering Vent OCC SASP
SASP = Supply Air Setpoint while in the
occupied vent mode
SET_PNT TEMPVOCC
T.VU XX F C 50 50 -20 TO 80 Tempr Vent Unocc SASP
SASP = Supply Air Setpoint while in the
unoccupied vent mode
SET_PNT TEMPVUNC
T.PRG XX F C 50 50 -20 TO 80 Tempering Purge SASP
SASP = Supply Air Setpoint while in the purge
mode
SET_PNT TEMPPURG