Specifications

39
Table 17 — Input Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CNN POINT
NAME
English SI
AQ.IN AQ.IN IAQ Inputs IAQ and Demand Ventilation Inputs
IAQ XXXX ppm ppm 0-2000 IAQ — PPM Indoor CO2 IAQ sensor input
SENSWORK
STATUS2
AIRQUALT
ANALOGIN
ECONMIN
IAQ
I.AQS TEXT LOW/HIGH IAQ — Discrete Input External command to increase outside air
STATUS2
AIRQUALT
ECONMIN
IAQIN
OAQ XXXX ppm ppm 0-2000 OAQ — PPM Outdoor CO2 Outdoor sensor input
AIRQUALT
ANALOGIN
ECONMIN
OAQ
DAQ XXXX ppm ppm 0-2000 Diff. Air Quality in PPM Differential air quality input
AIRQUALT
ECONMIN
DAQ
OA.RH XXX.X % % 0-100 Outside Air Rel. Humidity Outdoor air relative humidity sensor
ENTHALPY
STATUS2
ANALOGIN
ECONDIAG
OARH
OA.EN XXX.X calculated Outside Air Enthalpy Calculated from OAT and OA.RH (BTU/LB)
ECONWORK
ENTHALPY
ECONDIAG
OAE
OA.DP XXX.X F F calculated Outside Air Dewpoint
Outside air dewpoint temperature,
calculated from OA.RH and OAT
ENTHALPY
ECONDIAG
OADEWTMP
RA.RH XXX.X % % 0-100 Return Air Rel. Humidity Return air relative humidity sensor
ENTHALPY
STATUS2
ANALOGIN
ECONDIAG
RARH
RA.EN XXX.X calculated Return Air Enthalpy Calculated from RAT and RA.RH (BTU/LB)
ECONWORK
ENTHALPY
ECONDIAG
RAE
CS.IN CS.IN Current Sensor Inputs Compressor feedback digital inputs
CS.A1 TEXT ON/OFF Compressor A1 feedback Status of compressor A1 feedback signal
CIRCUIT A
COMPRWORK
CSB_A1
CS.A2 TEXT ON/OFF Compressor A2 feedback Status of compressor A1 feedback signal
CIRCUIT A
COMPWORK
CSB_A2
CS.B1 TEXT ON/OFF Compressor B1 feedback Status of compressor A1 feedback signal
CIRCUITB
COMPWORK
CSB_B1
CS.B2 TEXT ON/OFF Compressor B2 feedback Status of compressor A1 feedback signal
CIRCUITB
COMPWORK
CSB_B2
MISC MISC Miscellaneous Inputs Miscellaneous inputs
E.MPO XXX % % 0-100 Econo Min. Pos. Override
Used for remote min position and remote
economizer position control
SENSWORK
AIRQUALT
ECONMIN
IAQMINOV
DM.AI XXX % % 0-100 Remote Demand Limit 4-20 mA remote input
ANALOGIN
DMDLIMIT
DMDLMTMA
RM.SP XXX % % 0-20 EDT Setpoint or Setpoint ma Used for remote EDT setpoint control
ANALOGIN
DMDLIMIT
EDTRESMA
ENTER
ENTER
ENTER