Specifications
38
Table 17 — Input D
i
splay Menu
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric
STAT
STATS Thermostat Inputs Conventional thermostat inputs
TSTAT
INPUTS
Y1 TEXT — — ON/OFF Thermostat Y1 Input Thermostat cool stage 1
TSTAT
INPUTS
Y1
Y2 TEXT — — ON/OFF Thermostat Y2 Input Thermostat cool stage 2
TSTAT
INPUTS
Y2
W1 TEXT — — ON/OFF Thermostat W1 Input Thermostat heat stage 1
TSTAT
INPUTS
W1
W2 TEXT — — ON/OFF Thermostat W2 Input Thermostat heat stage 2
TSTAT
INPUTS
W2
G TEXT — — ON/OFF Thermostat G Input Thermostat fan on command
TSTAT
INPUTS
G
SW.IN SW.IN — — Switch Inputs Allows for reading of switch inputs
FIL.S TEXT — — DRT/CLN Filter Status Input Filter pressure drop switch
FLTSWORK
STATUS1
INPUTS
FLTS
FAN.S TEXT — — ON/OFF Supply Fan Status Input Fan differential pressure switch input
BLDGPRES
SFS_WORK
STATUS1
INPUTS
SFS
GAS.F TEXT — — ON/OFF Fan Request From IGC
only used on 48 Series units and is the com-
mand for fan operation from gas boards
INPUTS GASFAN
FDWN TEXT — — ON/OFF Fire Shutdown Input Smoke detector or field fire switch input
STATUS2
INPUTS
FSD
F.PRS TEXT — — ON/OFF Pressurization Input External command for pressurization
STATUS2
INPUTS
PRES
F.EVC TEXT — — ON/OFF Evacuation Input External command for evacuation
STATUS2
INPUTS
EVAC
F.PRG TEXT — — ON/OFF Fire Smoke Purge External command for Smoke Purge
STATUS2
INPUTS
PURG
E.ENA TEXT — — ON/OFF Remote Economizer Enable External command to enable economizer
ECONWORK
STATUS2
INPUTS
ECONENBL
E.OVR TEXT ON/OFF Econo Position Override External Command to open economizer
ECONWORK
STATUS2
ECONDIAG
ECONMIN
INPUTS
ECOORIDE
RE.MT TEXT — — ON/OFF Remote Input used for remote occupancy switch
STATUS2
INPUTS
RMTIN
DLM.1 TEXT — — ON/OFF Demand Limit Switch 1 External demand limit switch 1
STATUS2
DMDLIMIT
INPUTS
DMD_SW1
DLM.2 TEXT — — ON/OFF Demand Limit Switch 2 External demand limit switch 2
STATUS2
DMDLIMIT
INPUTS
DMD_SW2
ENTER
ENTER