Specifications

37
T
a
bl
e
16
S
etpo
i
nt
Di
sp
l
ay
M
enu
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
COOL
Cooling Setpoints Used to adjust cooling setpoint
OCSP XX.X F C 78.0 78.0 55to80 OccupiedCoolingSetpoint
Space or return air cooling
occupied setpoint
SET_PNT OHSP
UCSP XX.X F C 90.0 90.0 75 to 95 Unoccupied Cooling Setpoint
Space or return air
unoccupied setpoint
SET_PNT UCSP
NT.LO XX.X F C 50.0 50.0 40 to 70 Night Time Lockout Temp
Low Temperature protection
setpoint during purge
SET_PNT NTLO
V.C.ON XX.X F C 72.0 NA 55 to 85 VAV Occ. Cool On Setpnt
Return air temperature above
which cooling will start in
reset mode
SET_PNT VAVOCON
V.C.OF XX.X F C 2.0 NA 1 to 25 VAV Occ. Cool Off Delta
Return air temperature delta
below the V.C.ON which will
turn off cooling and go into
vent mode
SET_PNT VAVOCOFF
HEAT
Heating Setpoints Used to adjust heating setpoint
OHSP XX.X F C 68.0 68.0 55 to 80 Occupied Heating Setpoint
Space or return air occupied
setpoint used for heating
control
SET_PNT OHSP
UHSP XX.X F C 55.0 55.0 40 to 80 Unoccupied Heating Setpoint
Space or return air setpoint
unoccupied setpoint used for
heating control
SET_PNT UHSP
GAP GAP X.X F C 5.0 5.0 2.0 to 10.0 Heat-Cool Set Point Gap
Only applies to space temp
sensors
SET_PNT HCSP_GAP
SP.SP SP.SP X.X H2O Pa 1.5 NA 0.0 to 5.0 Static Pressure Setpoint
Supply air static pressure
setpoint used for VAV fan
speed control
SET_PNT SPSP
BP.SP BP.SP X.XX H2O Pa 0.05 0.05 -0.25 to 0.25 Building Pressure Setpoint
Building pressure static
setpoint used for control of
exhaust fans
SET_PNT BPSP
SA.SP SA.SP XX.X F C 55.0 55.0 45.0 to 75.0 Supply Air Setpoint
Unit supply air Temperature
Air Setpoint for VAV cooling
and economizer control
SET_PNT SASP
SA.SH SA.SH XXX F C 125.0 125.0 90.0 to 145 Heating Supply Air Setpt
Supply air temperature setpoint
for Staged Gas Heating
SET_PNT SASPHEAT
HI.SA HI.SA XX F C 55.0 55.0 45.0 to 75.0 Supply Air Setpoint HI
High Cool Setpoint for demand
cooling control
SET_PNT SASP_HI
LO.SA LO.SA XX F C 65.0 65.0 45.0 to 75.0 Supply Air Setpoint LO
Low Cool Setpoint for demand
cooling control
SET_PNT SASP_LO