Specifications

35
Table 14 — Temperature Display Menu
NOTE:
LAT = EDT for units operating in cool and heat has been off for several minutes.
LAT = Average of LAT.1, LAT.2, and LAT.3 for units with staged gas heat (LAT.1, LAT.2, and LAT.3 found in Temperatures, Unit Submode).
If EDT is in factory-installed position on fan then in heat LAT will not be available.
If EDT has been relocated to after heaters and unit is in heat then EDT will not be available.
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
FACTORY
DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
UNIT Unit Temperatures Allows for reading of temperatures
OAT XXX.X F C NA NA 40 to 240 Outside Air Temperature OAT Entering outdoor air hood
CAPACITY, ECONWORK,
ENTHALPY, STATUS1,
ANALOGIN, EDT_WORK
OAT
RAT XXX.X F C NA NA –40 to 240 Return Air Temperature
Return temperature inside unit, located
before return damper
ENTHALPY,
STATUS1, ANALOGIN,
ECONDIAG
RAT
MAT XXX.X F C NA NA –40 to 240 Mixed Air Temperature calculated value
CAPACITY, STATUS1,
ECONDIAG, EDT_WORK
MAT
EDT XXX.X F C NA NA –40 to 240
Evaporator Discharge
Tmp
See Note
CAPACITY, ECONWORK,
STATUS1, EDT_WORK
EDT
LAT XXX.X F C NA NA –40 to 240 Leaving Air Temperature See Note
STATUS1, ECONDIAG,
EDT_WORK
LAT
SPT XXX.X F C NA NA –40 to 240 Space Temperature only on units with T55/T56 Space Sensor STATUS1 ANALOGIN SPT
SPTO XXX.X F C NA NA 40 to 240 Space Temperature Offset only with T56 thermostats STATUS2 SPTO
LAT.1 XXX.X F C NA NA 40 to 240 Staged Gas LAT 1 Leaving air (Staged gas heat only) ANALOGIN, EDT_WORK LAT1SGAS
LAT.2 XXX.X F C NA NA 40 to 240 Staged Gas LAT 2 Leaving air (Staged gas heat only) ANALOGIN, EDT_WORK LAT2SGAS
LAT.3 XXX.X F C NA NA 40 to 240 Staged Gas LAT 3 Leaving air (Staged gas heat only) ANALOGIN, EDT_WORK LAT3SGAS
CIRC CIRC Circuit Temperatures Displays circuit refrigerant temperatures
SST.A XXX.X F C NA NA calculated Cir A Sat Suction Temp calculated from suction pressure CIRCUITA ANALOGIN SSTA
SCT.A XXX.X F C NA NA calculated Cir A Sat Condensing Tmp measured value (sensor on coil) CIRCUITA ANALOGIN SCTA
SST.B XXX.X F C NA NA calculated Cir B Sat Suction Temp calculated from suction pressure CIRCUITB ANALOGIN SSTB
SCT.B XXX.X F C NA NA calculated Cir B Sat Condensing Tmp measured value (sensor on coil) CIRCUITB ANALOGIN SCTB
CAL
CAL Calibrate Temperatures
Allows for calibration of temperatures
sensors
OAT.T XXX.X F C 0 0 –10 to 10 OAT Trim used for calibration of OAT sensor SENSCNFG OAT_TRIM
RAT.T XXX.X F C 0 0 –10 to 10 RAT Trim Used for calibration of RAT sensor SENSCNFG RAT_TRIM
SAT.T XXX.X F C 0 0 –10 to 10 SAT Trim Used for calibration of EDT sensor SENSCNFG SA_TRIM
SPT.T XXX.X F C 0 0 –10 to 10 Space Temp Trim used for calibration of SPT sensor SENSCNFG SPT_TRIM
SGT.T XXX.X F C 0 0 –30 to 30 Staged Gas LAT Avg Trim
Used for calibration of average SGT.T
sensors (LAT1, LAT2, LAT3)
SENSCNFG SGT_TRIM
CTA.T XXX.X F C 0 0 –30 to 30 Condensing Temp A Trim
Used for calibration of condensing
temperature sensor in cir A
SENSCNFG CTA_TRIM
CTB.T XXX.X F C 0 0 –30 to 30 Condensing Temp B Trim
Used for calibration of condensing
temperature sensor in cir B
SENSCNFG CTB_TRIM
ENTER
ENTER
ENTER