Specifications

34
T
a
bl
e13—
S
erv
i
ce
T
est
Di
sp
l
ay
M
enu
*Must be used on VAV units with electric or gas heat.
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric
STOP
STOP TEXT NO/YES Software Command Disable
Use to stop machine from running
(equivalent of an on-off switch)
TESTOUTS UNITSTOP
TEST
TEST TEXT OFF/ON Service Test Mode Will allow you to enter the test mode TESTOUTS MAN_CTRL
INDP
INDP Test Independent Outputs Allows testing of independent outputs
ECON XXX % % 0-100 Economizer Position Test will move economizer to % open, see Note TESTOUTS ECONCTST
E.PWR TEXT OFF/ON Economizer Power Test controls economizer power relay TESTOUTS ECONPTST
E.CAL TEXT NO/YES Calibrate Economizer? economizer will self calibrate TESTOUTS ECON_CAL
PE.A TEXT OFF/ON Power Exhaust Stage A Turn on Exhaust stage A TESTOUTS PE_A_TST
PE.B TEXT OFF/ON Power Exhaust Stage B Turn on Exhaust stage B TESTOUTS PE_B_TST
PE.C TEXT OFF/ON Power Exhaust Stage C Turn on Exhaust stage C TESTOUTS PE_C_TST
H.I.R. TEXT OFF/ON Heat Interlock Relay Test Turn on Heat Interlock Relay* TESTOUTS HIR_TST
ALR TEXT OFF/ON Remote Alarm Relay turn on alarm relay TESTOUTS ALRM_TST
FANS
FANS Test Fans Allows for test of fans and inverters
S.FAN TEXT OFF/ON Supply Fan Relay Turn on supply fan TESTOUTS SFAN_TST
S.VFD XXX % % 0-100 Supply Fan VFD Speed will drive inverter to % speed TESTOUTS SFVFDTST
OFC.A TEXT OFF/ON Condenser Fan A Turn on condenser fan stage A TESTOUTS CNDA_TST
OFC.B TEXT OFF/ON Condenser Fan B Turn on condenser fan stage B TESTOUTS CNDB_TST
COOL
COOL Test Cooling Allows for testing of compressor outputs
A1 TEXT OFF/ON Compressor A1 Relay Turn on compressor A1 and fans TESTOUTS CMPA1TST
A2 TEXT OFF/ON Compressor A2 Relay Turn on compressor A2 and fans TESTOUTS CMPA2TST
MLV TEXT OPN/CLS Minimum Load Valve Turn on Min load valve (valve open) TESTOUTS MLV_TST
B1 TEXT OFF/ON Compressor B1 Relay Turn on compressor B1 and fans TESTOUTS CMPB1TST
B2 TEXT OFF/ON Compressor B2 Relay Turn on compressor B2 and fans TESTOUTS CMPB2TST
HEAT
HEAT Heat Test Allows for test of heat stages
HS.1 TEXT OFF/ON Heat Stage 1 Turn on heat stage 1 TESTOUTS HS1_TST
HS.2 TEXT OFF/ON Heat Stage 2 Turn on heat stage 2 TESTOUTS HS2_TST
HS.3 TEXT OFF/ON Heat Stage 3 Turn on heat stage 3 (only staged gas) TESTOUTS HS3_TST
HS.4 TEXT OFF/ON Heat Stage 4 Turn on heat stage 4 (only staged gas) TESTOUTS HS4_TST
HS.5 TEXT OFF/ON Heat Stage 5 Turn on heat stage 5 (only staged gas) TESTOUTS HS5_TST
HS.6 TEXT OFF/ON Heat Stage 6 Turn on heat stage 6 (only staged gas) TESTOUTS HS6_TST
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER