Specifications
34
T
a
bl
e13—
S
erv
i
ce
T
est
Di
sp
l
ay
M
enu
*Must be used on VAV units with electric or gas heat.
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric
STOP
STOP TEXT — — NO/YES Software Command Disable
Use to stop machine from running
(equivalent of an on-off switch)
TESTOUTS UNITSTOP
TEST
TEST TEXT — — OFF/ON Service Test Mode Will allow you to enter the test mode TESTOUTS MAN_CTRL
INDP
INDP Test Independent Outputs Allows testing of independent outputs
ECON XXX % % 0-100 Economizer Position Test will move economizer to % open, see Note TESTOUTS ECONCTST
E.PWR TEXT — — OFF/ON Economizer Power Test controls economizer power relay TESTOUTS ECONPTST
E.CAL TEXT — — NO/YES Calibrate Economizer? economizer will self calibrate TESTOUTS ECON_CAL
PE.A TEXT — — OFF/ON Power Exhaust Stage A Turn on Exhaust stage A TESTOUTS PE_A_TST
PE.B TEXT — — OFF/ON Power Exhaust Stage B Turn on Exhaust stage B TESTOUTS PE_B_TST
PE.C TEXT — — OFF/ON Power Exhaust Stage C Turn on Exhaust stage C TESTOUTS PE_C_TST
H.I.R. TEXT — — OFF/ON Heat Interlock Relay Test Turn on Heat Interlock Relay* TESTOUTS HIR_TST
ALR TEXT — — OFF/ON Remote Alarm Relay turn on alarm relay TESTOUTS ALRM_TST
FANS
FANS Test Fans Allows for test of fans and inverters
S.FAN TEXT — — OFF/ON Supply Fan Relay Turn on supply fan TESTOUTS SFAN_TST
S.VFD XXX % % 0-100 Supply Fan VFD Speed will drive inverter to % speed TESTOUTS SFVFDTST
OFC.A TEXT — — OFF/ON Condenser Fan A Turn on condenser fan stage A TESTOUTS CNDA_TST
OFC.B TEXT — — OFF/ON Condenser Fan B Turn on condenser fan stage B TESTOUTS CNDB_TST
COOL
COOL Test Cooling Allows for testing of compressor outputs
A1 TEXT — — OFF/ON Compressor A1 Relay Turn on compressor A1 and fans TESTOUTS CMPA1TST
A2 TEXT — — OFF/ON Compressor A2 Relay Turn on compressor A2 and fans TESTOUTS CMPA2TST
MLV TEXT — — OPN/CLS Minimum Load Valve Turn on Min load valve (valve open) TESTOUTS MLV_TST
B1 TEXT — — OFF/ON Compressor B1 Relay Turn on compressor B1 and fans TESTOUTS CMPB1TST
B2 TEXT — — OFF/ON Compressor B2 Relay Turn on compressor B2 and fans TESTOUTS CMPB2TST
HEAT
HEAT Heat Test Allows for test of heat stages
HS.1 TEXT — — OFF/ON Heat Stage 1 Turn on heat stage 1 TESTOUTS HS1_TST
HS.2 TEXT — — OFF/ON Heat Stage 2 Turn on heat stage 2 TESTOUTS HS2_TST
HS.3 TEXT — — OFF/ON Heat Stage 3 Turn on heat stage 3 (only staged gas) TESTOUTS HS3_TST
HS.4 TEXT — — OFF/ON Heat Stage 4 Turn on heat stage 4 (only staged gas) TESTOUTS HS4_TST
HS.5 TEXT — — OFF/ON Heat Stage 5 Turn on heat stage 5 (only staged gas) TESTOUTS HS5_TST
HS.6 TEXT — — OFF/ON Heat Stage 6 Turn on heat stage 6 (only staged gas) TESTOUTS HS6_TST
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER