32
Table 12 — Run Status Display Menu
NOTE:
LAT = EDT for units operating in cool and heat has been off for several minutes.
LAT = Average of LAT.1, LAT.2, and LAT.3 for units with staged gas heat (LAT.1, LAT.2, and LAT.3 found in Temperatures, Unit Submode).
If EDT is in factory-installed position on fan then in heat LAT will not be available.
If EDT has been relocated to after heaters and unit is in heat then EDT will not be available.
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric
VIEW
VIEW Auto View of Run Status Scrolls automatically through the Displays
HVC.M TEXT see list Current HVAC Mode See mode list table MODES HVACMODE
EDT XXX.X F C –40 to 240
Evaporator Discharge
Tmp
See Note
CAPACITY,
ECONWORK,
STATUS1
EDT_WORK
EDT
LAT XXX.X F C –40 to 240 Leaving Air Temperature See Note
STATUS1,
ECONDIAG,
EDT_WORK
LAT
E.CPT XXX.X F C calculated Economizer Control Point supply air setpoint plus reset
ECONOWORK,
ECONDIAG
ECONCPNT
C.CPT XXX.X F C calculated Cooling Control Point
Control point for the leaving air tempera-
ture when mechanical cooling is being
used
CAPACITY C.CPT
H.CPT XXX.X F C calculated Heating Control Point
Control point for the leaving air
temperature in heating mode
——
SA.RS XXX.X F C calculated Supply Air Reset Amount
Amount of temperature reset being used
for supply air temperature
STATUS2 SASPRSET
LOD.F XXX % %' –100 to 100 Capacity Load Factor
+100% = Add a stage;
–100%= remove a stage
CAPACITY SMZ
C.CAP XXX % %' 0 to 100% Cooling % Total Capacity
% of Maximum unit nominal cooling
capacity
STATUS1 CCAP
H.CAP XXX % %' Heating % Total Capacity
% of Maximum unit nominal heating
capacity
STATUS1 HCAP
OCC TEXT YES/NO Occupied
Actual Operation will depend on
Unoccupied configuration
CONTROLLER-TIME OCC
TIME XX.XX HR:MIN HR:MIN 00.00-23.59 Time of Day Time of day in hr:minutes CONTROLLER-TIME TIMECOPY
ALRM XXXX
see alarm
table
Current Alarms & Alerts Number of Alarms CONTROLLER-TIME ALRMALRT
VERS VERS 1-?? Software Version Number
MBB TEXT MBB CESR131343-XX-XX
XX-XX is software version number
(ie 01-03)
VERSIONS MBB_SW
ECB1 TEXT ECB1 CESR131249-XX-XX Indicates the software that has been
loaded. (Only boards that are connected
will be displayed)
VERSIONS ECB1_SW
ECB2 TEXT ECB2 CESR131249-XX-XX VERSIONS ECB2_SW
NAVI TEXT NAVI CESR131227-XX-XX VERSIONS NAVI_SW
SCB TEXT SCB CESR131226-XX-XX VERSIONS SCB
CEM TEXT CEM CESR13174-XX-XX VERSIONS EMM_SW
MARQ TEXT MARQ CESR131171-XX-XX VERSIONS MARQ_SW
ENTER