Specifications

29
CONTROL FUNCTIONS
Overview —
The ComfortLink™ controls and software
have a large number of features that will meet the requirements
of broad range of applications. The controls are pre-configured
from the factory for the various factory-installed options, but
there will be field configurations required to setup the unit for
particular applications and field-installed accessories.
Common VAV and CV Standard Features:
Cooling capacity control of up to four compressors and one
minimum load valve (MLV), to maintain required space
conditions during occupied and unoccupied periods.
Automatic lead-lag of the compressors which changes at
full and zero load.
Minimum compressor on and off times for oil return and
compressor reliability.
Monitoring of suction pressure using pressure transducers
for diagnostics and coil freeze protection.
Control of two outdoor condenser fan contactors based on
saturated condensing temperature and outdoor air tempera-
ture for head pressure control.
Support of Motormaster® V control for low ambient head
pressure control if needed (the most energy efficient unit
will use an economizer and free cooling at low ambient con-
ditions).
Control of modulating economizer damper to provide free
cooling when outdoor conditions are suitable, using Supply-
Air Temperature as the basis of the control point A digitally
controlled economizer is used which provides diagnostic
feedback.
Economizer changeover control by dry bulb, differential dry
bulb, enthalpy, differential enthalpy or max dew point cus-
tom curve. Instead of the conventional enthalpy sensor or
switch, this control uses a dry bulb sensor and a humidity
sensor and then calculates the enthalpy. The standard A, B,
C, and D enthalpy changeover curves are also stored in the
software. Direct readout of the humidity is available as well
as other features due to the use of the humidity sensor.
Three-position economizer damper relay control for fixed
ventilation applications. Unit also has a mechanical 2-position
damper for applications that cannot use an economizer, but
require ventilation air for IAQ control.
Support of demand control ventilation through a reset of the
economizers minimum position. This reset based on differ-
ential CO
2
PPM (outdoor and indoor) can be chosen as
linear or as fast or slow-acting exponential curves.
Support of Remote Occupied/Unoccupied input to start/stop
the unit.
Control of the Economizer Damper and Indoor Fan to
obtain Night Time Free Cooling.
Pre-Occupancy IAQ Purge function.
Building Pressure control via four or six Power-Exhaust
Fan relay outputs. The building pressure sensor is read
directly by the ComfortLink controls and can be configured
through the unit display.
Demand Limit function based on demand limit switches or
demand limit 4 to 20 mA external signal or CCN Loadshed
POC commands.
Alarm monitoring of all key parameters.
Communications support on the CCN and LEN network.
Full electronic 365-day timeclock with backup capability.
Timeclock supports hour, minute, day of week, month, date
and year.
Daylight Savings Time function.
Occupancy control with 8 periods for unit operation.
Holiday Table containing up to 30 holidays within the
control.
Ability to initiate timed override from T55, T56 and T58
devices.
Ability to use multiple space temperature sensors (T55
only) to average Space Temperature external to the control.
Ability to support the CCN communicating T58 sensor.
Factory Test for end of production line tests.
Temperature Compensated Start algorithm to calculate early
start time before the occupancy period.
Linkage function for interface with a ComfortID™ system.
Support of Display, Maintenance, Configuration, Service,
and Set Point data tables for interface with Building
Supervisor, Service Tool, ComfortVIEW™, and Comfort-
WORKS® software.
Control of up to 6 relay outputs for gas or electric heat to
maintain a heating set point. Note that when this is used on
VAV systems the HIR (heat interlock relay) must be
connected to the terminal controls to drive the dampers
open.
Control using conventional (Y1, Y2, W1, W2, G) thermo-
stat inputs (TSTAT control) (CV only).
Ability to have up to 6 stages of capacity with a conven-
tional Y1, Y2, W1, W2 thermostat using a high and low
cooling and heat logic (CV only).
Support of a minimum load hot gas bypass valve for low
load applications. Valve is controlled directly by the control
and is an additional step of capacity as well as a low evapo-
rator protection device.
Adjustment of space set points (configurable amount ± 1 to
10° F) when using T-56 sensor (SPTO) (CV only).
Control of an Indoor Fan/Supply Fan relay.
Enable Heating or Cooling during Unoccupied periods as
required to maintain Space Temperature within the unoccu-
pied set points.
Provide Discrete inputs for Fan Status, Filter Status, and
Field Applied Status.
Provide an output for the external Alarm Light Indicator.
Integral return air smoke detector.
Smoke Control modes including Evacuation, Smoke Purge,
Pressurization, and Fire Shutdown (CEM required).
Provide power exhaust outputs for direct control of modu-
lated power exhaust stages during Fire/Smoke modes.
Enable Heating or Cooling during Unoccupied periods as
required by Nighttime thermostat inputs, or to maintain
Space Temperature or Return-Air Temperature within the
unoccupied set points.
VAV Only Standard Features:
Supply Duct Static Pressure Control by means of a 4 to 20
mA controlled VFD.
Support of external Supply Air Temperature Reset analog
input to reset supply air set point upward (CEM required).
Control of a heat-interlock relay, which must be used for
ensuring that the terminals are providing the minimum
CFM for heating.
Space Temperature Reset algorithm to reset Supply Air
set point upward when Space Temperature falls below its
occupied cooling set point.
Provide duct static pressure reset support for linkage with
air terminals.