Table 4 — ECB2 Channel Assignments
POINT NAME POINT DESCRIPTION I/O TYPE I/O POINT NAME
CONNECTOR
PIN NO.
INPUTS
—NotUsed DI1 J4, 1-2
—NotUsed DI2 J4, 3-4
BLDG Building Static Pressure 4-20 mA AN1 J5, 1-3
DUCT Supply Duct Static Pressure 4-20 mA AN2 J5, 4-6
OUTPUTS
S.VFD Supply Fan Inverter Speed 4-20 mA AO1 J9, 1-2
—NotUsed PP/MP J7, 1-3
—NotUsed RLY1 J8, 1-3
—NotUsed RLY 2 J8, 4-6
—NotUsed RLY 3 J8, 7-9
MLV Minimum Load Valve (Hot Gas Bypass) Relay RLY 6 J8, 16-18