CONTROLS SETUP CHECKLIST AND CONFIGURATION LOG (cont)
RECORD ALL SETPOINTS AND CONFIGURATIONS LISTED BELOW FOR FUTURE REFERENCE
SUBMODE
SUB
SUBMODE
ITEM SETTING
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
CMF.D
Comfort Demand Config Demand Control Setpoints
LC.ON F C 1.5 1.5 -1 TO 2.0 DMD Level Lo Cool On Used for Demand Driven Control Logic CDMD_CFG DMDLCON
LC.OF F C 1 1 0.5 TO 2.0 DMD Level (-) Lo Cool Off Used for Demand Driven Control Logic CDMD_CFG DMDLCOFF
HC.ON F C 0.5 0.5 0.5 TO 2.0 DMD Level(+) Hi Cool On Used for Demand Driven Control Logic CDMD_CFG DMDHCON
LH.ON F C 1.5 1.5 -1 TO 2.0 DMD Level Lo Heat On Used for Demand Driven Control Logic CDMD_CFG DMDLHON
LH.OF F C 1 1 0.5 TO 2.0 DMD Level (-) Low Heat Off Used for Demand Driven Control Logic CDMD_CFG DMDLHOFF
HH.ON F C 0.5 0.5 0.5 TO 2.0 DMD Level (+) Hit Heat On Used for Demand Driven Control Logic CDMD_CFG DMDHHON
CT.LV F C 0.1 0.1 0.1 TO 5 Cool Trend Demand Level Trend Temperature adjustment for demand cooling COOL_CFG CTRENDLV
CT.TM sec sec 60 60 30 TO 600 Cool Trend Time (secs) Trend time adjustment for demand cooling COOL_CFG CTRENDTM
HT.LV F C 0.1 0.1 0.1 TO 5 Heat Trend Demand Level Trend Temperature adjustment for demand heating HEAT_CFG HTRENDLV
HT.TM sec sec 60 60 30 TO 600 Heat Trend Time (sec) Trend time adjustment for demand heating HEAT_CFG HTRENDTM
RST
RST Supply Air Reset Config Supply air reset configurations
RST.T — — None None
0=NO RESET,
1=SPT RESET,
2=RAT RESET,
3=3RD PART RESET
Supply Air Reset Type Configures the type of supply air reset SET_PNT SARSTCFG
RTIO — — 3 3 0.0 TO 10.0 Reset Ratio Used for supply air reset control SET_PNT RTIO
R.LIM F C 10 10 0 TO 20.0 Reset Limit used for supply air reset control SET_PNT LIMT
DMD.L
DMD.L Demand Limit Config
DMLS — — none none
0=NO DEMAND LIMIT,
1=SWITCH,
2=4-20MA,
3=CCN LOADSHED
Demand Limit Select Used to configure demand limiting options
DMD_LIM,
DMDLIMIT
DMD_CTRL
D.L.20 % % 100 100 0-100 Demand Limit at 20 ma % demand limit at a 20 ma demand signal
DMD_LIM,
DMDLIMIT
DMT20MA
LS.GN — — 0 0 0 TO 99 Loadshed Group Number CCN loadshed group
DMD_LIM,
DMDLIMIT
SHED_NUM
LS.DD % % 0 0 0 TO 60 Loadshed Demand Delta Used for CCN Loadshed
DMD_LIM,
DMDLIMIT
SHED_DEL
LS.TM MIN MIN 60 60 0 TO 120 Maximum Loadshed Time Used for CCN Loadshed
DMD_LIM,
DMDLIMIT
SHED_TIM
DLS.1 % % 80 80 0 TO 100 Demand Limit SW.1 Setpt external switch controlled demand limit setpoint
DMD_LIM,
DMDLIMIT
DLSWSP1
DLS.2 % % 50 50 0 TO 100 Demand Limit SW.2 Setpt external switch controlled demand limit setpoint
DMD_LIM,
DMDLIMIT
DLSWSP2
CCN
CCN CCN Configuration
CCN.A — — 1 1 1 TO 239 CCN Address CCN Unit address number BRODEFS CCNADD
CCN.B — — 0 0 0 TO 239 CCN Bus Number CCN bus number BRODEFS CCNBUS
BAUD BITS/SEC BITS/SEC 9600 9600
2400, 4800, 9600,
19200, 38400
CCN Baud Rate
1=2400, 2=4800, 3=9600, 4=19200, 5=38400
CCN communication speed
BRODEFS CCNBAUDD
B.TIM — — OFF OFF ON/OFF CCN Time/Date Broadcast enable CCN Time/Date broadcast BRODEFS CCNBC
B.OAT — — OFF OFF ON/OFF CCN OAT Broadcast enable CCN OAT broadcast BRODEFS OATBC
B.ORH — — OFF OFF ON/OFF CCN OARH Broadcast enable CCN OARH broadcast BRODEFS OARHBC
B.OAQ — — OFF OFF ON/OFF CCN OAQ Broadcast enable CCN OAQ broadcast BRODEFS OAQBC
B.GS — — OFF OFF ON/OFF Global Schedule Broadcast enable CCN schedule broadcast BRODEFS GSBC
B.ACK — — OFF OFF ON/OFF CCN Broadcast ACK'ER enable CCN ACK'ER broadcast BRODEFS CCNCACK
ENTER