Specifications
CL-5
CONTROLS SETUP CHECKLIST AND CONFIGURATION LOG (cont)
RECORD ALL SETPOINTS AND CONFIGURATIONS LISTED BELOW FOR FUTURE REFERENCE
SUBMODE
SUB
SUBMODE
ITEM SETTING
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
IAQ
(cont)
PRG.E — — DSBL DSBL ENBL/DSBL IAQ Purge used to enable pre-occupancy purge
CONFIG,
AIRQUALT
PURGEN
PRG.D MIN MIN 5 5 5 TO 60 IAQ Purge Duration This is "how long do we purge." CONFIG IQPD
PG.LT % % 10 10 0 TO 100 IAQ Purge LOTemp Min Pos low limit on damper position during purge SET_PNT LTMP
PG.HT % % 35 35 0 TO 100 IAQ Purge HITemp Min Pos high limit on damper position during purge SET_PNT HTMP
OVR.P % % 100 100 0 TO 100 IAQ Econo Override Pos position of damper when override is in effect
AIR_QLTY,
AIRQUALT,
ECONMIN
IAQOVPOS
OA.CF — — No OAQ No OAQ
0=NO OAQ,
1=DCV OAQ,
2=LOKOUT
OAQ 4-20ma Sensor Config Used to configure OAQ sensor
AIR_QLTY,
AIRQUALT,
ECONMIN
OAQANCFG
OAQ.U — — 400 400 400-2000 User-Configured OAQ
Used to set the reference level for OAQ when there
is no OAQ sensor. Should be base on a locally
measure value and is typically around 450-550
AIR_QLTY OAQ_MEAS
OAQ.L ppm ppm 0 0 0 TO 2000 OAQ Lockout Value
above this outside air ppm level the dampers will
be closed to the min IAQ position
AIR_QLTY,
ECONMIN
OAQLOCK
AQD.L ppm ppm 100 100 0 TO 1000 Diff.Air Quality LOLimit
ppm level above outside air refrence for minimum
settingoftheIAQcurve
AIR_QLTY,
ECONMIN
DAQ_LOW
AQD.H ppm ppm 700 700 100 T0O 2000 Diff.Air Quality HiLimit
ppm level above outside air refrence for maximum
settingoftheIAQcurve
AIR_QLTY,
ECONMIN
DAQ_HIGH
DF.ON ppm ppm 400 400 0 TO 2000 DAQ PPM Fan On Setpoint used to control indoor fan on at ppm level ECONMIN FAQFNON
DF.OF ppm ppm 200 200 0 TO 2000 DAQ PPM Fan Off Setpoint used to control indoor fan off at ppm level
AIR_QLTY,
ECONMIN
DAQFNOFF
I.4M ppm ppm 0 0 0 TO 5000 IAQ Low Reference
used with remoted 4-20ma IAQ and is the ppm
level at 4 ma
SENSWORK,
AIRQUALT
ECONMIN
IAQREFL
I.20M ppm ppm 2000 2000 0 TO 5000 IAQ High Reference
used with remote 4-20ma IAQ and is the ppm level
at 20 ma
SENSWORK,
AIRQUALT
ECONMIN
IAQREFH
O.4M ppm ppm 0 0 0 TO 5000 OAQ Low Reference
used with remoted 4-20ma OAQ and is the ppm
level at 4 ma
SENSWORK,
AIRQUALT
ECONMIN
IAQREFL
O.20M ppm ppm 2000 2000 0 TO 5000 OAQ High Reference
used with remote 4-20ma OAQ and is the ppm
level at 20 ma
SENSWORK,
AIRQUALT
ECONMIN
IAQREFH
I.CRV ppm ppm 0 0 -5.0 TO 5.0 Diff.IAQ Responsiveness IAQ control curve responsiveness setting
AIR_QLTY,
ECONMIN
IAQREACT
OPTS
OPTS Option Sensor Config Option sensor configurations
EDT.R — — DSBL DSBL ENBL/DSBL EDT Reset Input enable remote reset signal feature UNIT EDTRSENS
ECO.S — — none none
0=NONE,
1=ECON ENABLE,
2=POSITION OVERRIDE
Economizer Switch
Used to configure the use of an economizer switch
and how it will be used
UNIT ECOSWCFG
FLS.E — — DSBL DSBL ENBL/DSBL Filter Stat.SW. Enabled? enable remote filter status switch use
FLTSWORK,
UNIT
FLTS_ENA
SPT.S — — DSPL DSPL ENBL/DSBL Space Temp Sensor enable use of T55, T56, T58 sensor UNIT SPTSENS
STO.S — — DSPL DSPL ENBL/DSBL Space Temp Offset Enable the use of T56 sensor offset feature UNIT SPTOSENS
STO.R F C 5 5 1 TO 10 SPT Offset Range (+/-) range for Offset feature adjustment UNIT SPTO_RNG
R.RH.S — — DSBL DSBL ENBL/DSBL Return Air RH Sensor enable the use of the return air humidity sensor
ENTHALPY,
UNIT
RARHSENS
O.RH.S — — DSBL DSBL ENBL/DSBL Ouside Air RH Sensor enable the use of an outside air humidity sensor
ENTHALPY,
UNIT
OARHSENS
DMT.S — — DSBL DSBL ENBL/DSBL Demand Limit Input enable the use of demand limit switch inputs
UNIT,
DMDLIMIT
DEMLSENS
RMT.C — — NONE NONE
0=NONE,
1=OCCUPANCY,
2=START STOP
Remote Switch Config
Used to configure the remote control switch and
how it will be used
SCHEDOVR RMTINCFG