Specifications

135
APPENDIX A — CCN POINTS (cont)
ECONMIN — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display ECONOCMD Econo Damper Command Pos YES XXX % 0 to 100% OUTPUTS E.PWR
Maintenance Display ECONOPOS Econo Damper Current Pos NO XXX % 0 to 100% OUTPUTS EC.AP
Maintenance Display MIN_POS Econo Current Min. Pos. NO XXX % 0 to 100% INPUT MENU E.MPO
Maintenance Display ECONOMIN Economizer Min.Position YES XXX % 0 to 100% CONFIGURATION MIN.P
Maintenance Display ECOORIDE Econo Position Override YES ON/OFF ON/OFF INPUT MENU E.OVR
Maintenance Display IAQMINOV Econ Min. Pos. Override YES XXX % 0 to 100%
Maintenance Display ECON_POT Econ Remote 10K Pot Val. YES XXXXX OHMS 0 TO 10000
Maintenance Display IAQ IAQ - PPM Indoor CO2 YES XXXXX PPM 0 TO 5000 INPUT MENU IAQ
Maintenance Display OAQ OAQ - PPM Outdoor CO2 YES XXXXX PPM 0 TO 5000
Maintenance Display IAQIN IAQ - Discrete Input YES High/Low High/Low INPUT MENU OAQ
Maintenance Display IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0 TO 100% CONFIGURATION AQ.MP
Maintenance Display IAQNCFG IAQ Minpos Sensor Config YES 0,1,2,3,4
0=MIN POS POT,
1=CNTL MIN POS,
2=OVERRIDE IAQ, 3=DCV,
4=NO IAQ
CONFIGURATION IA.CF
Maintenance Display IAQANFAN IAQ 4-20 ma Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=OVERRIDE IAQ
CONFIGURATION IA.FN
Maintenance Display IAQINCFG IAQ Discrete Input Config YES 0,1,2
0=NO IAQ, 1=DCV,
2=OVERRIDE IAQ
CONFIGURATION IA.I.C
Maintenance Display IAQINFAN IAQ Disc.In. Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=ALWAYS
CONFIGURATION IA.IF
Maintenance Display IAQOVPOS IAQ Econo Override Pos. YES XXX % 0 TO 100% CONFIGURATION OVR.P
Maintenance Display DAQ Diff.Air Quality in PPM NO XXXX PPM 0 TO 2000
Maintenance Display DAQ_LOW Diff.Air Quality LoLimit YES XXXX PPM 0 TO 1000 CONFIGURATION AQD.L
Maintenance Display DAQ_HIH Diff.Air Quality HiLimit YES XXXX PPM 0 TO 2000 CONFIGURATION AQD.H
Maintenance Display DAQFNOFF DAQ PPM Fan Off Setpoint YES XXXX PPM 0 TO 2000 CONFIGURATION DF.OF
Maintenance Display FAQFNON DAQ PPM Fan On Setpoint YES XXXX PPM 0 TO 2000 CONFIGURATION DF.ON
Maintenance Display IAQREACT Diff.IAQ Responsiveness YES X.X -5.0 to 5.0 CONFIGURATION I.CRV
Maintenance Display IAQREFL IAQ Low Reference YES XXXX 0 TO 5000 CONFIGURATION I.4M
Maintenance Display IAQREFH IAQ High Reference YES XXXX PPM 0 TO 5000 CONFIGURATION I.20M
Maintenance Display OAQLOCK OAQ Lockout Value YES XXXX.X PPM 0 TO 2000 CONFIGURATION OAQ.L
Maintenance Display OAQANCFG OAQ 4-20ma Sensor Config YES 0,1,2 NO OAQ, DCV OAQ, LOKOUT CONFIGURATION OA.CF
Maintenance Display IAQ_MA IAQ milliamps YES XX.XX mA 0 to 20
Maintenance Display OAQ_MA OAQ milliamps YES XX.XX mA 0 to 20
EDT_WORK — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display OAT Outside Air Temperature YES XXX.X F -40.0 TO 240.0 TEMPERATURES OAT
Maintenance Display EDT Evaporator DischargeTmp NO XXX.X F TEMPERATURES EDT
Maintenance Display LAT Leaving Air Temperature NO XXX.X F TEMPERATURES LAT
Maintenance Display MAT Mixed Air Temperature YES XXX.X F -40.0 TO 240.0 TEMPERATURES MAT
Maintenance Display RSETMATT Reset MAT Table? YES YES/NO CONFIGURATION R.MAT
Maintenance Display LAT_SGAS Staged Gas LAT Sum YES XXX.X F -40.0 TO 240.0
Maintenance Display LAT1SGAS Staged Gas LAT 1 YES XXX.X F -40.0 TO 240.0 TEMPERATURES LAT.1
Maintenance Display LAT2SGAS Staged Gas LAT 2 YES XXX.X F -40.0 TO 240.0 TEMPERATURES LAT.2
Maintenance Display LAT3SGAS Staged Gas LAT 3 YES XXX.X F -40.0 TO 240.0 TEMPERATURES LAT.3