Specifications

134
APPENDIX A — CCN POINTS (cont)
ECONDIAG — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display ECATIVE Economizer Active ? NO YES/NO YES/NO
Maintenance Display ECONOENBL Remote Economizer Enable YES ON/OFF ON/OFF INPUTS E.ENA
Maintenance Display ECON_HTH Economier heathy ? YES YES/NO YES/NO
Maintenance Display ECOORIDE Econo Position Override YES ON/OFF ON/OFF INPUTS E.OVR
Maintenance Display DBC_STAT DBC - OAT lockout ? NO YES/NO YES/NO
Maintenance Display DEW_STAT DEW - OA Dewpt.lockout? NO YES/NO YES/NO
Maintenance Display DDBCSTAT DDBC- OAT > RAT lockout? NO YES/NO YES/NO
Maintenance Display OAECSTAT OAEC- OA Enth Lockout? NO YES/NO YES/NO
Maintenance Display DEC_STAT DEC - Diff.Enth.Lockout? NO YES/NO YES/NO
Maintenance Display EDT_STAT EDT Sensor Bad? NO YES/NO YES/NO
Maintenance Display OAT_STAT OAT Sensor Bad ? NO YES/NO YES/NO
Maintenance Display ECONFORC Economizer foreced ? NO YES/NO YES/NO
Maintenance Display SFONSTAT Supply Fan not on 30s ? NO YES/NO YES/NO
Maintenance Display COOL_OFF Cool Mode not in effect? YES YES/NO YES/NO
Maintenance Display OAQLOCKD OAQ lockout in effect ? YES YES/NO YES/NO
Maintenance Display ECONHELD Econ recovery hold off ? YES YES/NO YES/NO
Maintenance Display RAT_LOW Return Temp too low ? NO YES/NO YES/NO
Maintenance Display OAT_STAT Outside Air Temperature YES XXX.X F -40 TO 240 INPUTS OAT
Maintenance Display OADEWTMP Outsideair DewPoint Temp NO XXX.X F 0 TO 100
Maintenance Display OARH Outside Air Rel.Humidity YES XXX.X % 0 TO 100% INPUTS OA.RH
Maintenance Display OAE Outdoor Enthalpy NO XX.XX BTU/LB 10 TO 50 INPUTS OA.E
Maintenance Display RAT Return Air Temperature YES XXX.X F -40 TO 240 TEMPERATURES RAT
Maintenance Display RARH Return Air RelHumidity YES XXX.X % 0 TO 100% INPUTS RA.RH
Maintenance Display RAE Return Air Enthalpy NO XX.XX BTU/LB 10 TO 50 INPUTS RA.E
Maintenance Display OAT_LOCK High OAT Lockout Temp YES XXX.X F 55 TO 120 CONFIGURATION OAT.L
Maintenance Display ECON_SEL Econ ChangeOver Select YES 0,1,23
0=DRY BULB, 1=DIFF. DB,
2=OA ENTHALPY,
3=DIFF ENTHALPY
CONFIGURATION E.CGO
Maintenance Display OAEC_SEL A,B,C,D Curve Select YES 0,1,2,3,4
0=A CURVE, 1=B CURVE,
2=C CURVE,
3=D CURVE, 4=CUSTOM
CURVE
CONFIGURATION OA.EC
Maintenance Display OAEN_CFG Outdr.Enth Compare Value YES XX.X BUT/LB 18.0 TO 28.0 CONFIGURATION OA.EN
Maintenance Display OADEWCFG OA Dewpoint Temp Limit YES XX.X F 50.0 TO 62.0 CONFIGURATION OA.DL
Maintenance Display SFAN Supply Fan State YES ON/OFF ON/OFF OUTPUTS S.FAN
Maintenance Display ECONOCMD Econo Damper Command Pos YES XXX % 0 TO 100% OUTPUTS E.PWR
Maintenance Display ECONOPOS Econo Damper Current Pos NO XXX % 0 TO 100% OUTPUTS EC.AP
Maintenance Display ECONCPNT Economizer Control Point YES XXX % 0 TO 100%
Maintenance Display MAT_SEL Estimate MAT? YES YES/NO YES/NO CONFIGURATION MAT.S
Maintenance Display MAT Mixed Air Temperature YES XXX.X F -40 TO 240 TEMPERATURES MAT
Maintenance Display EDT_STAT Evaporator Discharge Tmp YES XXX.X F -40 TO 240 TEMPERATURES EDT
Maintenance Display LAT Leaving Air Temperature YES XXX.X F -40 TO 240 TEMPERATURES LAT