Specifications
133
APPENDIX A — CCN POINTS (cont)
COMPWORK — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display CMPA1 Compressor A1 NO ON/OFF — ON/OFF OUTPUTS A1
Maintenance Display CSB_A1 Compressor A1 Feedback NO ON/OFF — ON/OFF INPUTS CS.A1
Maintenance Display CSBA1ASC Cur.Sens.Brd A1 Status YES Enable/Disabled — Enable/Disabled CONFIGURATION A1.C.E
Maintenance Display CSB_A1EN CSB A1 Feedback Alarm YES Enable/Dsable Enable/Dsable — —
Maintenance Display CMPA1LOK Comp A1 Locked Out ? NO YES/NO — YES/NO — —
Maintenance Display CMPA1STR Compressor A1 Strikes NO X — 0,1,2,3 — —
Maintenance Display CMPA1ENA Enable Compressor A1 YES Enable/Dsable — Enable/Dsable CONFIGURATION A1.EN
Maintenance Display CMPA2 Compressor A2 NO ON/OFF — ON/OFF OUTPUTS A2
Maintenance Display CSB_A2 Compressor A2 Feedback NO ON/OFF — ON/OFF INPUTS CS.A2
Maintenance Display CSBA2ASC Cur.Sens.Brd A2 Status YES Enable/Disabled — Enable/Disabled CONFIGURATION A2.C.E
Maintenance Display CSB_A2EN CSB A2 Feedback Alarm YES Enable/Dsable Enable/Dsable — —
Maintenance Display CMPA2LOK Comp A2 Locked Out ? NO YES/NO — YES/NO — —
Maintenance Display CMPA2STR Compressor A2 Strikes NO X — 0,1,2,3 — —
Maintenance Display CMPA2ENA Enable Compressor A2 YES Enable/Dsable — Enable/Dsable CONFIGURATION A2.EN
Maintenance Display CMPB1 Compressor B1 NO ON/OFF — ON/OFF OUTPUTS B1
Maintenance Display CSB_B1 Compressor B1 Feedback NO ON/OFF — ON/OFF INPUTS CS.B1
Maintenance Display CSBB1ASC Cur.Sens.Brd B1 Status YES Enable/Disabled — Enable/Disabled CONFIGURATION B1.C.E
Maintenance Display CSB_B1EN CSB B1 Feedback Alarm YES Enable/Dsable Enable/Dsable — —
Maintenance Display CMPB1LOK Comp B1 Locked Out ? NO YES/NO — YES/NO — —
Maintenance Display CMPB1STR Compressor B1 Strikes NO X — 0,1,2,3 — —
Maintenance Display CMPB1ENA Enable Compressor B1 YES Enable/Dsable — Enable/Dsable CONFIGURATION B1.EN
Maintenance Display VMPB2 Compressor B2 NO ON/OFF — ON/OFF OUTPUTS B2
Maintenance Display CSB_B2 Compressor B2 Feedback NO ON/OFF — ON/OFF INPUTS CS.B2
Maintenance Display CSBB2AC Cur.Sens.Brd B2 Status YES Enable/Disabled — Enable/Disabled CONFIGURATION B2.C.E
Maintenance Display CSB_B2EN CSB B2 Feedback Alarm YES Enable/Dsable Enable/Dsable — —
Maintenance Display CMPB2LOK Comp B2 Locked Out ? NO YES/NO — YES/NO — —
Maintenance Display CMPB2STR Compressor B2 Strikes NO X — 0,1,2,3 — —
Maintenance Display CMPB2ENA Enable Compressor B2 YES Enable/Dsable — Enable/Dsable CONFIGURATION B2.EN
Maintenance Display ALRESET Reset All Current Alarms YES YES/NO — YES/NO ALARMS R.CURR
DMDLIMIT — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display DEM_LIM Active Demand Limit YES XXX % 0 TO 100% INPUTS DM.AI
Maintenance Display DMD_CTRL Demand Limit Select YES 0,1,2,3 —
0=NO DEMAND LIMIT,
1=SWITCH, 2=4-20MA,
3=CCN LOADSHED
CONFIGURATION DMLS
Maintenance Display CAP_T Percent Total Capacity NO XXX % 0-100% — —
Maintenance Display DMD_SW1 Demand Limit Switch 1 YES ON/OFF — ON/OFF CONFIGURATION DLS.1
Maintenance Display DMD_SW2 Demand Limit Switch 2 YES ON/OFF — ON/OFF CONFIGURATION DLS.2
Maintenance Display DLSWSP1 Demand Limit Sw.1 Setpt YES XXX % 0-100% INPUTS DLM.1
Maintenance Display DLSWSP2 Demand Limit Sw.2 Setpt YES XXX % 0-100% INPUTS DLM.2
Maintenance Display DMDLMTMA 4-20 ma Demand signal YES X.XX ma 0 TO 20 — —
Maintenance Display DMT20MA Demand Limit at 20 mA YES XXX % 0-100% CONFIGURATION DL20
Maintenance Display DEMLSENS Demand Limit Input YES Enable/Dsable — Enable/Dsable CONFIGURATION DMT.S
Maintenance Display DL_STAT CCN Loadshed Signal NO X — ON/OFF — —
Maintenance Display SHED_NUM Loadshed Group Number YES XX — 0 TO 99 CONFIGURATION LS.GN
Maintenance Display SHED_DEL Loadshed Demand Delta YES XX % 0 TO 60 CONFIGURATION LS.DD
Maintenance Display SHED_TIM Maximum Loadshed Time YES XXX min 0 TO 120 CONFIGURATION LS.TM