Specifications

132
APPENDIX A — CCN POINTS (cont)
ALARMS — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display ALARM01C Active Alarm #1 YES AXXX
Alarms are shown as AXXX
Alerts are shown as TXXX,
PrealertsareshownasPXXX
——
Maintenance Display ALARM02C Active Alarm #2 YES AXXX
Maintenance Display ALARM03C Active Alarm #3 YES AXXX
Maintenance Display ALARM04C Active Alarm #4 YES AXXX
Maintenance Display ALARM05C Active Alarm #5 YES AXXX
Maintenance Display ALARM06C Active Alarm #6 YES AXXX
Maintenance Display ALARM07C Active Alarm #7 YES AXXX
Maintenance Display ALARM08C Active Alarm #8 YES AXXX
Maintenance Display ALARM09C Active Alarm #9 YES AXXX
Maintenance Display ALARM10C Active Alarm #10 YES AXXX
Maintenance Display ALARM11C Active Alarm #11 YES AXXX
Maintenance Display ALARM12C Active Alarm #12 YES AXXX
Maintenance Display ALARM13C Active Alarm #13 YES AXXX
Maintenance Display ALARM14C Active Alarm #14 YES AXXX
Maintenance Display ALARM15C Active Alarm #15 YES AXXX
Maintenance Display ALARM15C Active Alarm #16 YES AXXX
Maintenance Display ALARM15C Active Alarm #17 YES AXXX
Maintenance Display ALARM15C Active Alarm #18 YES AXXX
Maintenance Display ALARM15C Active Alarm #19 YES AXXX
Maintenance Display ALARM15C Active Alarm #20 YES AXXX
Maintenance Display ALARM15C Active Alarm #21 YES AXXX
Maintenance Display ALARM15C Active Alarm #22 YES AXXX
Maintenance Display ALARM15C Active Alarm #23 YES AXXX
Maintenance Display ALARM15C Active Alarm #24 YES AXXX
Maintenance Display ALARM15C Active Alarm #25 YES AXXX
ANALOGIN — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display DP_A Cir A Discharge Pressure NO XXX.X PSIG 0 to 450 psig PRESSURES SCP.A
Maintenance Display SCTA Cir A Sat Condensing Tmp NO XXX.X F -40 to 240 TEMPERATURES SCT.A
Maintenance Display DP_B Cir B Discharge Pressure NO XXX.X PSIG 0 to 450 psig PRESSURES SCP.B
Maintenance Display SCTB Cir B Sat Condensing Tmp NO XXX.X F -40 to 240 TEMPERATURES SCT.B
Maintenance Display SP_A Cir A Suction Pressure NO XXX.X PSIG 0 to 450 psig PRESSURES SSP.A
Maintenance Display SSTA Cir A Sat Suction Temp NO XXX.X F -40 to 240 TEMPERATURES SST.A
Maintenance Display SP_B Cir B Suction Pressure NO XXX.X PSIG 0 to 450 psig PRESSURES SSP.B
Maintenance Display SSTB Cir B Sat Suction Temp NO XXX.X F -40 to 240 TEMPERATURES SST.B
Maintenance Display RAT Return Air Temperature NO XXX.X F -40 to 240 TEMPERATURES RAT
Maintenance Display SAT Air Leaving Supply Fan NO XXX.X F -40 to 240
Maintenance Display OAT Outside Air Temperature NO XXX.X F -40 to 240 TEMPERATURES OAT
Maintenance Display SPT Space Temperature NO XXX.X F -40 to 240 TEMPERATURES SPT
Maintenance Display SPT0 Space Temperature Offset NO XXX.X F -40 to 240 TEMPERATURES SPT0
Maintenance Display IAQ IAQ - PPM Indoor Level NO XXXX PPM 0 to 5000
Maintenance Display BP Building Pressure NO X.XXX IN H2O -26 to +.26 PRESSURES BLDG
Maintenance Display SP Duct Static Pressure NO X.XXX IN H2O 0 to 5 PRESSURES DUCT
Maintenance Display LAT1SGAS Staged Gas LAT 1 NO XXX.X F -40 to 240 TEMPERATURES LAT.1
Maintenance Display LAT2SGAS Staged Gas LAT 2 NO XXX.X F -40 to 240 TEMPERATURES LAT.2
Maintenance Display LAT3SGAS Staged Gas LAT 3 NO XXX.X F -40 to 240 TEMPERATURES LAT.3
Maintenance Display DMDLMTMA 4-20 ma Demand Signal NO XX.XX mA 0 to 20 ma INPUTS DM.AI
Maintenance Display OAQ OAQ - PPM Outdoor CO2 NO XXXX PPM 0 to 5000
Maintenance Display OARH Outside Air Rel.Humdity NO XXX.X % 0 TO 100% INPUTS OA.RH
Maintenance Display RARH Return Air Rel.Humidity NO XXX.X % 0 TO 100% INPUTS RA.RH