Specifications

131
APPENDIX A — CCN POINTS (cont)
AIRQUALT — MAINTENANCE
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Maintenance Display OAQLOCK OAQ Lockout Value YES XXXX PPM 0 TO 2000 CONFIGURATION OAQ.L
Maintenance Display IAQINCFG IAQ Discrete Input Confg YES 0,1,2
0=NO IAQ, 1=DCV,
2=OVERRIDE IAQ
Maintenance Display IAQOVPOS IAQ Econo Override Pos. YES XXX % 0 TO 100% CONFIGURATION OVR.P
Maintenance Display IAQANCFG IAQ Minpos Sensor Config YES 0,1,2,3,4
0=MIN POS POT,
1=CNTL MIN POS,
2=OVERRIDE IAQ, 3=DCV,
4=NO IAQ
CONFIGURATION IA.CF
Maintenance Display IAQINFAN IAQ Disc.In. Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=ALWAYS
CONFIGURATION IA.IF
Maintenance Display IAQANFAN IAQ 4-20 ma Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=OVERRIDE IAQ
CONFIGURATION IA.FN
Maintenance Display OAQANCFG OAQ 4-20ma Sensor Config YES 0,1,2
0=NO OAQ, 1=DCV OAQ,
2=LOKOUT
CONFIGURATION OA.CF
Maintenance Display IAQREACT Diff .IAQ Responsiveness YES XX -5.0 to 5.0 CONFIGURATION I.CRV
Maintenance Display DAQ Diff.Air Quality in PPM NO XXXX
Maintenance Display DAQ_LOW Diff.Air Quality LoLimit YES XXXX PPM 0 TO 1000 CONFIGURATION AQD.L
Maintenance Display DAQ_HIGH Diff .Air Quality HiLimit YES XXXX PPM 0 TO 2000 CONFIGURATION AQD.H
Maintenance Display DAQFNOFF DAQ PPM Fan Off Setpoint YES XXXX PPM 0 TO 2000 CONFIGURATION DF.OF
Maintenance Display DAQFNON DAQ PPM Fan On Setpoint YES XXXX PPM O TO 2000 CONFIGURATION DF.ON
Maintenance Display IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0 TO 100% CONFIGURATION AQ.MP
Maintenance Display ECONOMIN Economizer Min.Position YES XXX % 0 TO 100% CONFIGURATION MIN.P
Maintenance Display IAQREFL IAQ Low Reference YES XXXX PPM 0 TO 5000 CONFIGURATION I.4M
Maintenance Display IAQREFH IAQ High Reference YES XXXX PPM 0 TO 5000 CONFIGURATION I.20M
Maintenance Display OAQREFL OAQ Low Reference YES XXXX PPM 0 TO 5000
Maintenance Display OAQREFH OAQ High Reference YES XXXX PPM 0 TO 5000
Maintenance Display IAQ_MA IAQ milliamps YES XX.XX mA 0 TO 20.0
Maintenance Display OAQ_MA OAQ milliamps YES XX.XX mA 0 TO 20.0
Maintenance Display IAQ IAQ - PPM Return CO2 YES XXXX PPM 0 TO 5000
Maintenance Display IAQMINOV Econ Min. Pos. Override YES XXX % 0 TO 100%
Maintenance Display OAQ OAQ - PPM Return CO2 YES XXXX PPM 0 TO 5000
Maintenance Display IAQIN IAQ Discrete Input YES Low/High Low/High INPUTS I.AQS
Maintenance Display MIN_POS Econo Current Min. Pos. NO XXX % INPUTS E.MPO
Maintenance Display IAQL IAQ Low Alert limit YES XXXX PPM 0 TO 5000
Maintenance Display IAQH IAQ high alert limit YES XXXX PPM 0 TO 5000
Maintenance Display PURG Smoke Purge Input YES ON/OFF ON/OFF INPUTS F.PRG
Maintenance Display PURGEN IAQ Purge YES Enable/Dsable Enable/Dsable CONFIGURATION PRG.E