Specifications
129
APPENDIX A — CCN POINTS (cont)
UNIT — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration CTRLTYPE Unit Control Type YES 1,2,3,4,5,6 —
1=SPT 2STAGE,
2=SPT MULTI,
3=TSTAT 2STAGE,
4= TSTAT MULTI,
5=VAV RAT, 6=VAV SPT
CONFIGURATION CTL.T
Configuration SIZE Sz (20,25,27,30,35,40,50,60) YES XX TONS 20 TO 60 CONFIGURATION SIZE
Configuration VARSFAN Variable Speed Fan? YES YES/NO — YES/NO CONFIGURATION VS.FN
Configuration ECON_ENA Economizer Installed? YES YES/NO — YES/NO CONFIGURATION EC.EQ
Configuration ECON_CTL Economizer Control Type YES 1,2,3 — 1,2,3 CONFIGURATION E.CTL
Configuration ECTRMENA Enable Economizer Trim YES Enable/Dsable — Enable/Dsable CONFIGURATION TRM-E
Configuration ECOSWCFG Economizer Switch Config YES 0,1,2 —
0=NONE, 1=ECON ENABLE,
2=POSITION OVERRIDE
CONFIGURATION ECO.S
Configuration MAT_SEL Estimate MAT? YES YES/NO — YES/NO CONFIGURATION MAT.S
Configuration RATSENS Return Air Temp Sensor YES Enable/Dsable — Enable/Dsable — --
Configuration SPTSENS Space Temp Sensor YES Enable/Dsable — Enable/Dsable CONFIGURATION SPT.S
Configuration SPTOSENS Space Temp Offset YES Enable/Dsable — Enable/Dsable CONFIGURATION STO.S
Configuration SPTO_RNG SPT Offset Range (+/-) YES XX F 1 to 10 CONFIGURATION STO.R
Configuration SPSENS Duct Static Press Sensor YES Enable/Dsable — Enable/Dsable CONFIGURATION SP.S
Configuration BPSENS Building Static Pressure Sensor YES Enable/Dsable — Enable/Dsable CONFIGURATION BP.S
Configuration OARHSENS Outside Air RH Sensor YES Enable/Dsable — Enable/Dsable CONFIGURATION O.RH.S
Configuration RARHSENS Return Air RH Sensor YES Enable/Dsable — Enable/Dsable CONFIGURATION R.RH.S
Configuration EDTRSENS EDT Reset Input YES Enable/Dsable — Enable/Dsable CONFIGURATION EDT.R
Configuration DEMLSENS Demand Limit Input YES Enable/Dsable — Enable/Dsable CONFIGURATION DMT.S
Configuration FLTS_ENA Filter Stat.Sw.Enabled? YES Enable/Dsable — Enable/Dsable CONFIGURATION FLS.E
Configuration DP_TRANS Discharge Press. Transducer YES YES/NO — YES/NO CONFIGURATION DP.XR
Configuration HPSP Head Pressure Setpoint YES XXX.X F 80.0 to 150.0 CONFIGURATION HP.SP
Configuration MM_SEL Motor Master Installed? YES YES/NO — YES/NO CONFIGURATION S.MM
Configuration DELAY Minutes Off Time YES XX MIN 0 TO 15 CONFIGURATION DELY
Configuration ECB1_BRD ECB1 Module Installed YES YES/NO — YES/NO CONFIGURATION ECB1
Configuration ECB2_BRD ECB2 Module Installed YES YES/NO — YES/NO CONFIGURATION ECB2
Configuration SCB_BRD SCB Module Installed YES YES/NO — YES/NO CONFIGURATION SCB
Configuration EMM_BRD CEM Module Installed YES YES/NO — YES/NO CONFIGURATION CEM
ALRTLMITS — DIAGNOSITCS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Service Configuration SPLO SPT LO Alert Limit/Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION SPL.O
Service Configuration SPHO SPT HI Alert Limit/Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION SPH.O
Service Configuration SPLU SPT LO Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION SPL.U
Service Configuration SPHU SPT HI Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION SPH.U
Service Configuration SAL SAT LO Alert Limit/Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION SAL.O
Service Configuration SAH SAT HI Alert Limit Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION SAH.O
Service Configuration SALU SAT LO Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION SAL.U
Service Configuration SALH SAT HI Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION SAH.U
Service Configuration RAL RAT LO Alert Limit/Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION RAL.O
Service Configuration RAH RAT HI Alert Limit/Occ YES XXX.X F -10.0 TO 245.0 CONFIGURATION RAH.O
Service Configuration RALU RAT LO Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION RAL.U
Service Configuration RAHU RAT HI Alert Limit/Unocc YES XXX.X F -10.0 TO 245.0 CONFIGURATION RAH.U
Service Configuration RHL RH Low Alert Limit YES XXX % -10.0 TO 245.0 CONFIGURATION IRH.L
Service Configuration RHH RH High Alert Limit YES XXX % -10.0 TO 245.0 CONFIGURATION IRH.H
Service Configuration SPL SP Low Alert Limit YES X.X in H2O 0.0 TO 5.0 CONFIGURATION DP.L
Service Configuration SPH SP High Alert Limit YES X.X in H2O 0.0 TO 5.0 CONFIGURATION DP.H
Service Configuration BPLO BP Low Alert Limit YES X.XX in H2O -.26 TO .26 CONFIGURATION BP.L
Service Configuration BPHI BP High Alert Limit YES X.XX in H2O -.26 TO .26 CONFIGURATION BP.H
Service Configuration IAQL IAQ High Alert Limit YES XXXX PPM 0 TO 5000 CONFIGURATION IQ.HI