APPENDIX A — CCN POINTS (cont)
SET_PNT — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Setpoint Configuration OHSP Occupied Heat Setpoint YES XXX.X F 55.0 TO 80 SETPOINT OHSP
Setpoint Configuration OCSP Occupied Cool Setpoint YES XXX.X F 55.0 TO 80 SETPOINT OC.SP
Setpoint Configuration UHSP Unoccupied Heat Setpoint YES XXX.X F 40.0 TO 80 SETPOINT UHSP
Setpoint Configuration UCSP Unoccupied Cool Setpoint YES XXX.X F 75.0 TO 95.0 SETPOINT UCSP
Setpoint Configuration HCSP_GAP Heat-Cool Setpoint Gap YES XXX.X F 2.0 TO 10 SETPOINT GAP
Setpoint Configuration VAVOCON VAV Occ. Cool On Setpnt YES XXX F 55 TO 85 SETPOINT V.C.ON
Setpoint Configuration VAVOCOFF VAV Occ. Cool Off Delta YES XXX F 1 TO 25 SETPOINT V.C.OF
Setpoint Configuration SPSP Static Pressure Setpoint YES XXX.X in H2O 0 TO 5.0 SETPOINT SP.SP
Setpoint Configuration BPSP Building Pressure Setp. YES XX.XX in H2O -.25 TO .25 SETPOINT BP.SP
Setpoint Configuration SASP Supply Air Setpoint YES XXX.X F 45.0 TO 75.0 SETPOINT SA.SP
Setpoint Configuration SASP_HI Supply Air Setpoint Hi YES XXX.X F 45.0 TO 75.0 SETPOINT HI.SA
Setpoint Configuration SASP_LO Supply Air Setpoint Lo YES XXX.X F 45.0 TO 75.0 SETPOINT LO.SA
Setpoint Configuration SASPHEAT Heating Supply Air Setpt YES XXX.X F 90 TO 145 SETPOINT SA.S.H
Setpoint Configuration SASPTEMP Temper Supply Air Setpt YES XXX.X F 5 TO 100 SETPOINT SA.SH
Setpoint Configuration TEMPCOOL Tempering in Cool SASP YES XXX — -20 TO 40.0 CONFIGURATION T.CL
Setpoint Configuration TEMPVOCC Tempering Vent Occ SASP YES XXX — -20 TO 40.0 CONFIGURATION T.VO
Setpoint Configuration TEMPVUNC Temper Vent Unocc. SASP YES XXX — -20 TO 40.0 CONFIGURATION T.VU
Setpoint Configuration TEMPPURG Tempering Purge SASP YES XXX — -20 TO 40.0 CONFIGURATION T.PRG
Setpoint Configuration NTLO Night Time Lockout Temp YES XXX.X F 40.O TO 70.0 SETPOINT NT.LO
Setpoint Configuration SARSTCFG Supply Air Reset Type YES 0,1,2,3 —
0=NO RESET, 1=SPT RESET,
2=RAT RESET, 3=3RD PART
RESET
CONFIGURATION RST.T
Setpoint Configuration RTIO Reset Ratio YES XXX.X — 0.0 TO 10.0 CONFIGURATION RTIO
Setpoint Configuration LIMT Reset Limit YES XXX.X F 0 TO 20.0 CONFIGURATION R.LIM
Setpoint Configuration LSP Demand Limit Setpoint YES XXX % 0 TO 100% — —
Setpoint Configuration ECONOMIN Economizer Min.Position YES XXX % 0 TO 100% CONFIGURATION MIN.P
Setpoint Configuration IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0 TO 100% CONFIGURATION AQ.MP
Setpoint Configuration PE1_POS PE Stage1 Econo Position YES XXX % 0 TO 100% CONFIGURATION PE1.P
Setpoint Configuration PE2_POS PE Stage2 Econo Position YES XXX % 0 TO 100% CONFIGURATION PE2.P
Setpoint Configuration OACS Outside Air CFM Setpoint YES XXXX CFM NOT USED AT THIS TIME — —
Setpoint Configuration LTMP IAQ Purge LoTemp Min Pos YES XXX % 0 TO 100% CONFIGURATION PG.LT
Setpoint Configuration HTMP IAQ Purge HiTemp Min Pos YES XXX % 0 TO 100% CONFIGURATION PG.HT
Setpoint Configuration OADEWCFG OA Dewpoint Temp Limit YES XXX.X F 50.0 TO 62.0 CONFIGURATION OA.DL
SFANVFD — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration SPKP Prop. Gain SF VFD YES XX.X — 0.0 TO 99.9 CONFIGURATION SP.KP
Configuration SPKD Diff. Gain SF VFD YES XX.X — 0 TO 50.0 CONFIGURATION SP.KD
Configuration SPKI Integral Gain SF VFD YES X.X — 0.0 TO 50.0 CONFIGURATION SP.KI
Configuration SPK System Gain SF VFD YES X.X — 0.0 TO 50.0 CONFIGURATION SP.K
Configuration VFD_TIME VFD PID Time (seconds) YES X — 1 TO 200 CONFIGURATION SP.DT
Configuration SVFD_MIN IDF VFD Minimum Speed YES XXX % LEAVE AT 0% CONFIGURATION SF.MN
Configuration SVFD_MAX IDF VFD Maximum Speed YES XXX % 0-100% CONFIGURATION SF.MX
Configuration SVFD_FSD IDF Speed in Fire Mode YES XXX % 0-100% CONFIGURATION SF.FS