Specifications

128
APPENDIX A — CCN POINTS (cont)
SET_PNT — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Setpoint Configuration OHSP Occupied Heat Setpoint YES XXX.X F 55.0 TO 80 SETPOINT OHSP
Setpoint Configuration OCSP Occupied Cool Setpoint YES XXX.X F 55.0 TO 80 SETPOINT OC.SP
Setpoint Configuration UHSP Unoccupied Heat Setpoint YES XXX.X F 40.0 TO 80 SETPOINT UHSP
Setpoint Configuration UCSP Unoccupied Cool Setpoint YES XXX.X F 75.0 TO 95.0 SETPOINT UCSP
Setpoint Configuration HCSP_GAP Heat-Cool Setpoint Gap YES XXX.X F 2.0 TO 10 SETPOINT GAP
Setpoint Configuration VAVOCON VAV Occ. Cool On Setpnt YES XXX F 55 TO 85 SETPOINT V.C.ON
Setpoint Configuration VAVOCOFF VAV Occ. Cool Off Delta YES XXX F 1 TO 25 SETPOINT V.C.OF
Setpoint Configuration SPSP Static Pressure Setpoint YES XXX.X in H2O 0 TO 5.0 SETPOINT SP.SP
Setpoint Configuration BPSP Building Pressure Setp. YES XX.XX in H2O -.25 TO .25 SETPOINT BP.SP
Setpoint Configuration SASP Supply Air Setpoint YES XXX.X F 45.0 TO 75.0 SETPOINT SA.SP
Setpoint Configuration SASP_HI Supply Air Setpoint Hi YES XXX.X F 45.0 TO 75.0 SETPOINT HI.SA
Setpoint Configuration SASP_LO Supply Air Setpoint Lo YES XXX.X F 45.0 TO 75.0 SETPOINT LO.SA
Setpoint Configuration SASPHEAT Heating Supply Air Setpt YES XXX.X F 90 TO 145 SETPOINT SA.S.H
Setpoint Configuration SASPTEMP Temper Supply Air Setpt YES XXX.X F 5 TO 100 SETPOINT SA.SH
Setpoint Configuration TEMPCOOL Tempering in Cool SASP YES XXX -20 TO 40.0 CONFIGURATION T.CL
Setpoint Configuration TEMPVOCC Tempering Vent Occ SASP YES XXX -20 TO 40.0 CONFIGURATION T.VO
Setpoint Configuration TEMPVUNC Temper Vent Unocc. SASP YES XXX -20 TO 40.0 CONFIGURATION T.VU
Setpoint Configuration TEMPPURG Tempering Purge SASP YES XXX -20 TO 40.0 CONFIGURATION T.PRG
Setpoint Configuration NTLO Night Time Lockout Temp YES XXX.X F 40.O TO 70.0 SETPOINT NT.LO
Setpoint Configuration SARSTCFG Supply Air Reset Type YES 0,1,2,3
0=NO RESET, 1=SPT RESET,
2=RAT RESET, 3=3RD PART
RESET
CONFIGURATION RST.T
Setpoint Configuration RTIO Reset Ratio YES XXX.X 0.0 TO 10.0 CONFIGURATION RTIO
Setpoint Configuration LIMT Reset Limit YES XXX.X F 0 TO 20.0 CONFIGURATION R.LIM
Setpoint Configuration LSP Demand Limit Setpoint YES XXX % 0 TO 100%
Setpoint Configuration ECONOMIN Economizer Min.Position YES XXX % 0 TO 100% CONFIGURATION MIN.P
Setpoint Configuration IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0 TO 100% CONFIGURATION AQ.MP
Setpoint Configuration PE1_POS PE Stage1 Econo Position YES XXX % 0 TO 100% CONFIGURATION PE1.P
Setpoint Configuration PE2_POS PE Stage2 Econo Position YES XXX % 0 TO 100% CONFIGURATION PE2.P
Setpoint Configuration OACS Outside Air CFM Setpoint YES XXXX CFM NOT USED AT THIS TIME
Setpoint Configuration LTMP IAQ Purge LoTemp Min Pos YES XXX % 0 TO 100% CONFIGURATION PG.LT
Setpoint Configuration HTMP IAQ Purge HiTemp Min Pos YES XXX % 0 TO 100% CONFIGURATION PG.HT
Setpoint Configuration OADEWCFG OA Dewpoint Temp Limit YES XXX.X F 50.0 TO 62.0 CONFIGURATION OA.DL
SFANVFD — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration SPKP Prop. Gain SF VFD YES XX.X 0.0 TO 99.9 CONFIGURATION SP.KP
Configuration SPKD Diff. Gain SF VFD YES XX.X 0 TO 50.0 CONFIGURATION SP.KD
Configuration SPKI Integral Gain SF VFD YES X.X 0.0 TO 50.0 CONFIGURATION SP.KI
Configuration SPK System Gain SF VFD YES X.X 0.0 TO 50.0 CONFIGURATION SP.K
Configuration VFD_TIME VFD PID Time (seconds) YES X 1 TO 200 CONFIGURATION SP.DT
Configuration SVFD_MIN IDF VFD Minimum Speed YES XXX % LEAVE AT 0% CONFIGURATION SF.MN
Configuration SVFD_MAX IDF VFD Maximum Speed YES XXX % 0-100% CONFIGURATION SF.MX
Configuration SVFD_FSD IDF Speed in Fire Mode YES XXX % 0-100% CONFIGURATION SF.FS