Specifications

121
APPENDIX A — CCN POINTS (cont)
STATUS2 — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display SPTO Space Temperature Offset YES XX.X F -10 TO +10 TEMPERATURES SPT0
Status Display SASPRSET Supply Air Setpnt Reset NO XX.X F 0 to 15
Status Display SPRESET Static Pressure Reset YES XX.X 0 to 5
Status Display ECONENBL Remote Economizer Enable YES On/Off On/Off INPUTS E.ENA
Status Display ECOORIDE Econo Position Override YES On/Off On/Off INPUTS E.OVR
Status Display RMTIN Remote Input YES On/Off On/Off INPUTS RE.MT
Status Display EMSTOP Emergency Stop YES Enable/Disable Enable/Disable
Status Display RARH Return Air Rel.Humidity YES XXX % 0-100% INPUTS RA.RH
Status Display OARH Outside Air Rel.Humidity YES XXX % 0-100% INPUTS OA.RH
Status Display IAQ IAQ - PPM Return CO2 YES XXXX PPM 0 TO 5000 INPUTS IAQ
Status Display IAQIN IAQ - Discrete Input YES Low/High % LOW/HIGH INPUTS I.AQS
Status Display EVAC Evacuation Input YES On/Off On/Off INPUTS F.EVC
Status Display PRES Pressurization Input YES On/Off On/Off INPUTS F.PRS
Status Display PURG Smoke Purge Input YES On/Off On/Off INPUTS F.PRG
Status Display FSD Fire Shutdown Input YES On/Off On/Off INPUTS FDWN
Status Display DMD_SW1 Demand Limit Switch 1 YES On/Off On/Off INPUTS DLM.1
Status Display DMD_SW2 Demand Limit Switch 2 YES On/Off On/Off INPUTS DLM.2
TSTAT — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display Y1 Thermostat Y1 Input YES On/Off On/Off INPUTS Y1
Status Display Y2 Thermostat Y2 Input YES On/Off On/Off INPUTS Y2
Status Display W1 Thermostat W1 Input YES On/Off On/Off INPUTS W1
Status Display W2 Thermostat W2 Input YES On/Off On/Off INPUTS W2
Status Display G Thermostat G Input YES On/Off On/Off INPUTS G
AIR_QLTY — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration IAQINCFG IAQ Discrete Input Confg YES 0,1,2
0=NO IAQ, 1=DCV,
2=OVERRIDE IAQ
CONFIGURATION IA.I.C
Configuration IAQOVPOS IAQ Econo Override Pos. YES XXX % 0 TO 100% CONFIGURATION OVR.P
Configuration IAQANCFG IAQ Minpos Sensor Config YES 0,1,2,3,4
0=MIN POS POT,
1=CNTL MIN POS,
2=OVERRIDE IAQ,
3=DCV, 4=NO IAQ
CONFIGURATION IA.CF
Configuration IAQINFAN IAQ Disc.In. Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=ALWAYS
CONFIGURATION IA.IF
Configuration IAQANFAN IAQ 4-20 ma Fan Config YES 0,1,2
0=NEVER, 1=OCCUPIED,
2=OVERRIDE IAQ
CONFIGURATION IA.FN
Configuration OAQANCFG OAQ 4-20 ma Sensor Config YES 0,1,2
0=NO OAQ, 1=DCV OAQ,
2=LOKOUT
CONFIGURATION OA.CF
Configuration OAQ_USER User Determined OAQ YES XXX 400-2000 CONFIGURATION OAQ-U