Specifications

120
APPENDIX A — CCN POINTS (cont)
SENSWORK — POINTS
*Not used.
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display IAQREFL IAQ Low Reference YES XXXX PPM 0 to 5000 CONFIGURATION I.4M
Status Display IAQREFH IAQ High Reference YES XXXX PPM 0 to 5000 CONFIGURATION I.20M
Status Display IAQ_MA IAQ milliamps YES X.XX 0 to 20.0
Status Display OAQ_MA OAQ milliamps YES X.XX 0 to 20.0
Status Display IAQ IAQ - PPM Indoor CO2 YES XXX 0 to 5000 INPUTS IAQ
Status Display IAQMINOV Econ Min. Pos. Override YES X % 0 to 100%
Status Display BP Building Pressure NO X.XXX in H2O PRESSURES BP
Status Display BP_RANGE Bldg Press (+/-) Range YES X.XX in H2O 0 to 1.0 CONFIGURATION BP.R
Status Display SP Duct Static Pressure NO X.XX in H2O PRESSURES DUCT
Status Display SP_LOW Duct Press Sensor Lo End YES X.XX -10 to 10 CONFIGURATION SP.H.L
Status Display SP_HIGH Duct Press Sensor Hi End YES X.XX -10 to 10 CONFIGURATION SP.L.L
SFS_WORK — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display SFS Supply Fan Status Input YES On/Off On/Off INPUTS FAN.S
Status Display SFAN Supply Fan State YES On/Off On/Off OUTPUTS S.FAN
Status Display SP Duct Static Pressure NO X.XX in H2O PRESSURES DUCT
Status Display SFS_MON Fan Stat Monitoring Type YES 0, 1, 2 F 0 to 2 CONFIGURATION IF.M
Status Display SFS_SHUT Fan fail shuts down unit YES yes/no % Yes/No CONFIGURATION IS.FS
Status Display SFSLOGIC Fan Status Sw. Normally: YES open/close in H2O Open/Closed CONFIGURATION SFS.L
STATUS1 — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display SPT Space Temperature YES XXX.X F -40 to 240 TEMPERATURES SPT
Status Display EDT Evaporator Discharge Tmp NO XXX.X F TEMPERATURES EDT
Status Display LAT Leaving Air Temperature NO XXX.X F TEMPERATURES LAT
Status Display RAT Return Air Temperature YES XXX.X F -40 to 240 TEMPERATURES RAT
Status Display MAT Mixed Air Temperature YES XXX.X F -40 to 240 TEMPERATURES MAT
Status Display CLSP* Control Setpoint NO XXX.X F 40 to 90
Status Display CCAP Cooling % Total Capacity NO XXX.X % 0-100% RUN STATUS CCAP
Status Display HCAP Heating % Total Capacity NO XXX.X % 0-100% RUN STATUS HCAP
Status Display ECACTIVE Economizer Active ? NO yes/no yes/no
Status Display SFS Supply Fan Status Input YES On/Off on/off INPUTS FAN.S
Status Display SFAN Supply Fan State YES On/Off on/off OUTPUTS S.FAN
Status Display SP Duct Static Pressure NO X.XX in H2O 0 to 5 PRESSURES DUCT
Status Display OAT Outside Air Temperature YES XXX.X F -40 to 240 TEMPERATURES OAT
Status Display MIN_POS Econo Current Min. Pos. NO XXX % 0 to 100 INPUTS E.MPO
Status Display BP Building Pressure NO X.XXX in H2O -.26 to .26 PRESSURES BLDG
Status Display PED Power Exhaust Damper Pos YES XXX % 0-100% CONFIGURATION PE1.P
Status Display FLTS Filter Status Input YES XXXX Dirty/Clean INPUTS FIL.S