APPENDIX A — CCN POINTS (cont)
ENTHALPY — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display ALTITUDE Altitude........in feet: YES XXXX FT 0-9999 — —
Status Display ATMOPRES Atmospheric Pressure NO XX.XXX in Hg 20-35 INHg — —
Status Display OAE Outdoor Air Enthalpy NO XX.XX BTU/LB 18-28 BTU/LB INPUTS OA.E
Status Display OAT Outside Air Temperature YES XXX.X F -40 TO 240 F TEMPERATURES OAT
Status Display OARH Outside Air Rel.Humidity YES XXX.X % 0-100% INPUTS OA.RH
Status Display OARHSENS Outside Air RH Sensor YES XXX — Enable/Disable CONFIGURATION O.RH.S
Status Display OADEWCFG OA Dewpoint Temp Limit YES XXX.X F 50 to 62 CONFIGURATION OA.DL
Status Display OADEWTMP OutsideAir DewPoint Temp NO XXX.X F 0 to 100% — —
Status Display OA_HUMR OutsideAir Humidty Ratio NO X.XXXXX — 0 to 100% — —
Status Display OA_PWS OA H2O Vapor Sat.Pressur NO X.XXX in Hg — —
Status Display OA_PW OA H2O Partial.Press.Vap NO X.XXXXX in Hg — —
Status Display RAE Return Air Enthalpy NO X.XX BTU/LB INPUTS RA.E
Status Display RAT Return Air Temperature YES XXX.X F -40 TO 240 F TEMPERATURES RAT
Status Display RETURN_T Controlling Return Temp YES XXX.X F -40 TO 240 F — —
Status Display RARH Return Air Rel.Humidity YES XXX.X % 0 to 100% INPUTS RA.RH
Status Display RATSENS Return Air Temp Sensor YES Enable/Disable — Enable/Disable — —
Status Display RARHSENS Return Air RH Sensor YES Enable/Disable — Enable/Disable — —
FLTSWORK — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display SFAN Supply Fan State YES ON/OFF — ON/OFF OUTPUTS S.FAN
Status Display FLTS Filter Status Input YES Clean/Dirty — Clean/Dirty INPUTS FIL.S
Status Display FLTSLOGC Filter Status Normally: YES Open/Closed — Open/Closed CONFIGURATION FTS.L
Status Display FLTS_ENA Filter Stat.Sw.Enabled ? YES Enable/Disable — Enable/Disable CONFIGURATION FLS.E
HEATSTAT — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display HS1 Heat Stage 1 NO On/Off — On/Off OUTPUTS HS.1
Status Display HS1_TG Heat Stage 1 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H1
Status Display HS2 Heat Stage 2 NO On/Off — On/Off OUTPUTS HS.2
Status Display HS2_TG Heat Stage 2 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H2
Status Display HS3 Heat Stage 3 NO On/Off — On/Off OUTPUTS HS.3
Status Display HS3_TG Heat Stage 3 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H3
Status Display HS4 Heat Stage 4 NO On/Off — On/Off OUTPUTS HS.4
Status Display HS4_TG Heat Stage 4 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H4
Status Display HS5 Heat Stage 5 NO On/Off — On/Off OUTPUTS HS.5
Status Display HS5_TG Heat Stage 5 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H5
Status Display HS6 Heat Stage 6 NO On/Off — On/Off OUTPUTS HS.6
Status Display HS6_TG Heat Stage 6 Timeguard NO XXXX SEC 0-1000 RUN STATUS TG.H6
Status Display HIR Heat Interlock Relay NO On/Off — On/Off OUTPUTS —
Status Display HTSTGTYP Heat Stage Type YES 1,2,3,4 —
0=2 stage; 1=4 stage;
2=5 stage;
3=9 stage; 4=11 stage
CONFIGURATION N.HST
Status Display HTCAPMAX Max Cap Change per Cycle YES XX.X % 0-100% CONFIGURATION S.CP.M
Status Display HTOCCENA Occupied Heating Enabled YES Yes/No — Yes/No CONFIGURATION OCC.H
Status Display HTSGPIDR PID algorithm rate YES XX — 90-300 CONFIGURATION S.PI.R
Status Display HTSGRISE Heat Rise dF/sec Clamp YES X.XX — 0.06 to 0.20 CONFIGURATION S.RIS
Status Display HT_DGAIN Derivative Gain YES X.X — 0.0 to 1.5 CONFIGURATION S.DGN
Status Display HT_PGAIN Proportional Gain YES X.X — 1.0 to 1.5 CONFIGURATION S.P.GN
Status Display HT_MR_DB S.Gas DB min.dF/PID Rate YES X.X — 0.5 to 5.0 — —
Status Display HT_SG_DB St.Gas Temp. Dead Band YES X.X F 2.0 to 5.0 CONFIGURATION S.DB